Tripp Lite UPS Device - Statistics
Description
Monitors key metrics for Tripp Lite devices, providing insights into the device’s status, main load state, temperature, and total output active power. The following metrics are monitored:
- Device Status
- Main Load State
- Temperature (Celsius)
- Total Output Active Power
These metrics are collected via the following SNMP OIDs:
- Device Status:
1.3.6.1.4.1.850.1.1.1.2.1.10
- Device Name:
1.3.6.1.4.1.850.1.1.1.2.1.6
- Main Load State:
1.3.6.1.4.1.850.1.1.3.1.2.1.1.1
- Temperature (Celsius):
1.3.6.1.4.1.850.1.1.3.1.2.1.1.7
- Total Output Active Power:
1.3.6.1.4.1.850.1.1.3.1.2.1.1.12
Validated Model: Tripp Lite SMART500RT1U
SysObjectOID: 1.3.6.1.4.1.850.1.1.1
Software Version: PowerAlert 20.2.0 (Build 922)
Prerequisites
None
Supported Metric
Monitor Name | Metric Name | Metric Display Name | Unit | Description |
---|---|---|---|---|
Tripp Lite Device Status | tripplite_device_Status | Tripp Lite Device Status | Monitors the Tripp Lite Device Status. [ TRIPPLITE-PRODUCTS :: tlpDeviceStatus : 1.3.6.1.4.1.850.1.1.1.2.1.10 ] | |
Tripp Lite UPS Device - Statistics | tripplite_ups_device_MainLoadState | Tripp Lite UPS Device Main Load State | Monitors the Tripp Lite UPS Device Main Load State. [ TRIPPLITE-PRODUCTS :: tlpUpsDeviceMainLoadState : 1.3.6.1.4.1.850.1.1.3.1.2.1.1.1 ]. Possible values are 0: unknown, 1: off, 2: on | |
tripplite_ups_device_TemperatureC | Tripp Lite UPS Device Temperature Celsius | Celsius | Monitors the Tripp Lite UPS Device Temperature Celsius. [ TRIPPLITE-PRODUCTS :: tlpUpsDeviceTemperatureC : 1.3.6.1.4.1.850.1.1.3.1.2.1.1.7 ] | |
tripplite_ups_device_TotalOutputActivePower | Tripp Lite UPS Device Total Output Active Power | W | Monitors the Tripp Lite UPS Device Total Output Active Power. [ TRIPPLITE-PRODUCTS :: tlpUpsDeviceOutputActivePowerTotal : 1.3.6.1.4.1.850.1.1.3.1.2.1.1.12 ] |
Tripp Lite UPS Battery
Description
This monitor tracks key battery statistics for Tripp Lite UPS devices, including:
- Battery Status
- Estimated Charge Remaining
- Voltage
- Capacity
- Charge
- Condition
- Age
These metrics are collected via the following SNMP OIDs:
- Battery Voltage:
1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.1
- Battery Capacity:
1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.3
- Battery Charge:
1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.4
- Battery Status:
1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.1
- Estimated Charge Remaining:
1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.4
- Battery Condition:
1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.1
- Battery Age:
1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.4
Validated Model: Tripp Lite SMART500RT1U
SysObjectOID: 1.3.6.1.4.1.850.1.1.1
Software Version: PowerAlert 20.2.0 (Build 922)
Prerequisites
None
Supported Metric
Monitor Name | Metric Name | Metric Display Name | Unit | Description |
---|---|---|---|---|
Tripp Lite UPS Battery - Performance | tripplite_ups_battery_Voltage | Tripp Lite UPS Battery Voltage | Monitors the Tripp Lite UPS battery detail voltage, which indicates the current battery voltage level. [ TRIPPLITE-PRODUCTS :: tlpUpsBatteryDetailVoltage : 1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.1 ] | |
tripplite_ups_battery_Capacity | Tripp Lite UPS Battery Capacity | % | Monitors the Tripp Lite UPS Battery Capacity. The estimated remaining battery capacity is expressed as a percentage of the full capacity. [ TRIPPLITE-PRODUCTS :: tlpUpsBatteryDetailCapacity : 1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.3 ] | |
tripplite_ups_battery_Charge | Tripp Lite UPS Battery Charge | Monitors the Tripp Lite UPS Charge state of the battery. [ TRIPPLITE-PRODUCTS :: tlpUpsBatteryDetailCharge : 1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.4 ]. Possible values are 0: floating, 1: charging, 2: resting, 3: discharging, 4: normal, 5: standby. | ||
Tripp Lite UPS Battery - Statistics | tripplite_ups_battery_Status | Tripp Lite UPS Battery Status | Monitors the Tripp Lite UPS Battery Status, which is the indication of the capacity remaining in the UPS system's batteries. [ TRIPPLITE-PRODUCTS :: tlpUpsBatteryStatus : 1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.1 ]. Possible Values are 1: unknown, 2: batteryNormal, 3: batteryLow, 4: batteryDepleted. | |
tripplite_ups_battery_EstimatedChargeRemaining | Tripp Lite UPS Battery Estimated Charge Remaining | % | Monitors the Tripp Lite UPS estimate of the battery charge remaining expressed as a percentage of full charge. [ TRIPPLITE-PRODUCTS :: tlpUpsEstimatedChargeRemaining : 1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.4 ] | |
Tripp Lite UPS Battery Pack - Details | tripplite_ups_battery_Condition | Tripp Lite UPS Battery Condition | Monitors the Tripp Lite UPS Battery Condition. The condition of the battery. A bad battery should be replaced. [ TRIPPLITE-PRODUCTS :: tlpUpsBatteryPackDetailCondition : 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.1 ]. Possible values are 0: unknown, 1: good, 2: weak, 3: bad. | |
tripplite_ups_battery_Age | Tripp Lite UPS Battery Age | Days | Monitors the age of the Tripp Lite UPS battery in tenths of years. This is equal to the current date minus tlpUpsBatteryPackDetailLastReplaceDate. [ TRIPPLITE-PRODUCTS :: tlpUpsBatteryPackDetailAge : 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.4 ] |
Tripp Lite UPS Input
Description
This integration monitors key input phase statistics for Tripp Lite UPS devices, including:
- Input Phase Frequency
- Input Phase Voltage
- Input Transformer Status These statistics denote the current status of the transformer, indicating whether it is reducing or boosting the input.
These metrics are collected via the following SNMP OIDs:
- Input Phase Frequency:
1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.2
- Input Phase Voltage:
1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.3
- Input Transformer Status:
1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.13
Validated Model: Tripp Lite SMART500RT1U
SysObjectOID: 1.3.6.1.4.1.850.1.1.1
Software Version: PowerAlert 20.2.0 (Build 922)
Prerequisites
None
Supported Metrics
Monitor Name | Metric Name | Metric Display Name | Unit | Description | Tripp Lite UPS Input Phase - Statistics | tripplite_ups_inputphase_Frequency | Tripp Lite UPS Input Phase Frequency | Hz | Monitors the Tripp Lite UPS present input frequency for a given input line. [ TRIPPLITE-PRODUCTS :: tlpUpsInputPhaseFrequency : 1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.2 ]. |
---|---|---|---|---|
tripplite_ups_inputphase_Voltage | Tripplite UPS Input Phase Voltage | V | Monitors the Tripplite UPS Input Phase Voltage which is the magnitude of the present input voltage for a given input line. [ TRIPPLITE-PRODUCTS :; tlpUpsInputPhaseVoltage : 1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.3 ] | |
Tripp Lite UPS Input Transformer Status | tripplite_ups_input_TransformerStatus | Tripp Lite UPS Input Transformer Status | v | Monitors the Tripp Lite UPS Input Transformer Status which Denotes the status of the transformer as to whether it is presently reducing or boosting the input. [ TRIPPLITE-PRODUCTS :: tlpUpsInputTransformerStatus : 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.13 ]. Possible Values are 0: normal, 1: reducing, 2: boosting. |
Tripp Lite UPS Output
Description
This integration monitors key output metrics for Tripp Lite UPS devices, including:
- Output Source
- Nominal Voltage
- Frequency
- Output Line Statistics, such as:
- Voltage
- Current
- Active Power
- Utilization
These metrics are collected via the following SNMP OIDs:
- Output Source:
1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.1
- Output Frequency:
1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.3
- Output Line Voltage:
1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.2
- Output Line Current:
1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.3
- Output Line Active Power:
1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.4
- Output Line Utilization:
1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.5
Validated Model: Tripp Lite SMART500RT1U
SysObjectOID: 1.3.6.1.4.1.850.1.1.1
Software Version: PowerAlert 20.2.0 (Build 922)
Supported Metrics
Monitor Name | Metric Name | Metric Display Name | Unit | Description | Tripp Lite UPS Output | tripplite_ups_output_Source | Tripp Lite UPS Output Source | Hz | Monitors the Tripp Lite UPS Output Source.The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the device has an open circuit breaker. Possible values are 0: unknown, 1: other, 2: none, 3: normal(3) 4: bypass, 5: battery, 6: boosting, 7: reducing, 8: second, 9: economy, 10: testing. |
---|---|---|---|---|
tripplite_ups_output_Frequency | Tripp Lite UPS Output Frequency | Hz | Monitors the Tripplite UPS Output Frequency in Hertz. [ TRIPPLITE-PRODUCTS :: tlpUpsOutputFrequency : 1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.3 ] | Tripp Lite UPS Output Line - Statistics | tripplite_ups_outpuline_Voltage | Tripp Lite UPS Output Line Voltage | Hz | Monitors the Tripp Lite UPS Output Line Voltage which is the the magnitude of the present output voltage for a given output line.[ TRIPPLITE-PRODUCTS :: tlpUpsOutputLineVoltage : 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.2 ]. |
tripplite_ups_outpuline_Current | Tripp Lite UPS Output Line Current | amps | Monitors the Tripp Lite UPS Output Line Current. The output current, in hundredths of amps, for a given line. [ TRIPPLITE-PRODUCTS :: tlpUpsOutputLineCurrent : 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.3 ]. | |
tripplite_ups_outpuline_ActivePower | Tripp Lite UPS Output Line Active Power | Watts | Monitors the Tripp Lite UPS Output Line Active Power.The present output true power. [ TRIPPLITE-PRODUCTS :: tlpUpsOutputLineActivePower : 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.4 ]. | |
tripplite_ups_outpuline_Utilization | Tripp Lite UPS Output Line Utilization | % | Monitors the Tripp Lite UPS Output Line Utilization.The percentage of the ups power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA. [ TRIPPLITE-PRODUCTS :: tlpUpsOutputLineUtilization : 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.5 ]. |
Tripp Lite UPS Outlet
Description
Monitors important outlet-related metrics for Tripp Lite UPS devices, including:
- Outlet State
- Outlet Circuit
- Outlet Phase
These metrics are collected via the following SNMP OIDs:
- Outlet State:
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.4
- Outlet Circuit:
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.16
- Outlet Phase:
1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.17
Validated Model: Tripp Lite SMART500RT1U
SysObjectOID: 1.3.6.1.4.1.850.1.1.1
Software Version: PowerAlert 20.2.0 (Build 922)
Prerequisites
None
Supported Metrics
Monitor Name | Metric Name | Metric Display Name | Unit | Description |
---|---|---|---|---|
Tripp Lite UPS Outlet - Statistics | tripplite_ups_outlet_State | Tripp Lite UPS Outlet State | Monitors the Tripp Lite UPS current state of the outlet. [ PRODUCTS :: tlpUpsOutletState : 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.4 ]. Possible Values are 0: unknown, 1: off, 2: on. | |
tripplite_ups_outlet_Phase | Tripplite UPS Outlet Phase | Monitors the Tripplite UPS Outlet Phase. Indicates on which phase or phases the given outlet is associated. [ TRIPPLITE-PRODUCTS :: tlpUpsOutletPhase : 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.17 ]. Possible values are 0: unknown, 1: phase1, 2: phase2, 3: phase3, 4: phase1-2, 5: phase2-3, 6: phase3-1. |
Tripp Lite UPS Battery Replace Days
Description
This monitor tracks the number of days since the Tripp Lite UPS system’s batteries were last replaced, as well as the number of days remaining until the next scheduled battery replacement.
The following metrics are monitored:
- Last Replace Date: The number of days since the UPS batteries were last replaced.
- Next Replace Date: The number of days until the next scheduled UPS battery replacement.
These metrics are collected via the following SNMP OIDs:
- Last Replace Date:
1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.5
- Next Replace Date:
1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.6
Validated Model: Tripp Lite SMART500RT1U
SysObjectOID: 1.3.6.1.4.1.850.1.1.1
Software Version: PowerAlert 20.2.0 (Build 922)
Prerequisites
None
Supported Metrics
Monitor Name | Metric Name | Metric Display Name | Unit | Description |
---|---|---|---|---|
Tripp Lite UPS Battery Replace Days | tripplite_ups_battery_LastReplaceDays | Tripp Lite UPS Battery Last Replace Days | Days | This monitor provides the number of days since the Tripp Lite UPS system's batteries were last replaced. [ TRIPPLITE-PRODUCTS :: upsBasicBatteryLastReplaceDate - 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.5 ]. |
tripplite_ups_battery_NextReplaceDays | Tripp Lite UPS Battery Next Replace Days | Days | This monitor provides the number of days until the Tripp Lite UPS system's batteries are scheduled to be replaced. [ TRIPPLITE-PRODUCTS :: tlpUpsBatteryPackDetailNextReplaceDate - 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.6 ]. |