Tripp Lite UPS Device - Statistics

Description

Monitors key metrics for Tripp Lite devices, providing insights into the device’s status, main load state, temperature, and total output active power. The following metrics are monitored:

  • Device Status
  • Main Load State
  • Temperature (Celsius)
  • Total Output Active Power

These metrics are collected via the following SNMP OIDs:

  • Device Status: 1.3.6.1.4.1.850.1.1.1.2.1.10
  • Device Name: 1.3.6.1.4.1.850.1.1.1.2.1.6
  • Main Load State: 1.3.6.1.4.1.850.1.1.3.1.2.1.1.1
  • Temperature (Celsius): 1.3.6.1.4.1.850.1.1.3.1.2.1.1.7
  • Total Output Active Power: 1.3.6.1.4.1.850.1.1.3.1.2.1.1.12

Validated Model: Tripp Lite SMART500RT1U
SysObjectOID: 1.3.6.1.4.1.850.1.1.1
Software Version: PowerAlert 20.2.0 (Build 922)

Prerequisites

None

Supported Metric

Monitor NameMetric NameMetric Display NameUnitDescription
Tripp Lite Device Statustripplite_device_StatusTripp Lite Device StatusMonitors the Tripp Lite Device Status. [ TRIPPLITE-PRODUCTS :: tlpDeviceStatus : 1.3.6.1.4.1.850.1.1.1.2.1.10 ]
Tripp Lite UPS Device - Statisticstripplite_ups_device_MainLoadStateTripp Lite UPS Device Main Load StateMonitors the Tripp Lite UPS Device Main Load State. [ TRIPPLITE-PRODUCTS :: tlpUpsDeviceMainLoadState : 1.3.6.1.4.1.850.1.1.3.1.2.1.1.1 ]. Possible values are 0: unknown, 1: off, 2: on
tripplite_ups_device_TemperatureCTripp Lite UPS Device Temperature CelsiusCelsiusMonitors the Tripp Lite UPS Device Temperature Celsius. [ TRIPPLITE-PRODUCTS :: tlpUpsDeviceTemperatureC : 1.3.6.1.4.1.850.1.1.3.1.2.1.1.7 ]
tripplite_ups_device_TotalOutputActivePowerTripp Lite UPS Device Total Output Active PowerWMonitors the Tripp Lite UPS Device Total Output Active Power. [ TRIPPLITE-PRODUCTS :: tlpUpsDeviceOutputActivePowerTotal : 1.3.6.1.4.1.850.1.1.3.1.2.1.1.12 ]

Tripp Lite UPS Battery

Description

This monitor tracks key battery statistics for Tripp Lite UPS devices, including:

  • Battery Status
  • Estimated Charge Remaining
  • Voltage
  • Capacity
  • Charge
  • Condition
  • Age

These metrics are collected via the following SNMP OIDs:

  • Battery Voltage: 1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.1
  • Battery Capacity: 1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.3
  • Battery Charge: 1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.4
  • Battery Status: 1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.1
  • Estimated Charge Remaining: 1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.4
  • Battery Condition: 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.1
  • Battery Age: 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.4

Validated Model: Tripp Lite SMART500RT1U
SysObjectOID: 1.3.6.1.4.1.850.1.1.1
Software Version: PowerAlert 20.2.0 (Build 922)

Prerequisites

None

Supported Metric

Monitor NameMetric NameMetric Display NameUnitDescription
Tripp Lite UPS Battery - Performancetripplite_ups_battery_VoltageTripp Lite UPS Battery VoltageMonitors the Tripp Lite UPS battery detail voltage, which indicates the current battery voltage level. [ TRIPPLITE-PRODUCTS :: tlpUpsBatteryDetailVoltage : 1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.1 ]
tripplite_ups_battery_CapacityTripp Lite UPS Battery Capacity%Monitors the Tripp Lite UPS Battery Capacity. The estimated remaining battery capacity is expressed as a percentage of the full capacity. [ TRIPPLITE-PRODUCTS :: tlpUpsBatteryDetailCapacity : 1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.3 ]
tripplite_ups_battery_ChargeTripp Lite UPS Battery ChargeMonitors the Tripp Lite UPS Charge state of the battery. [ TRIPPLITE-PRODUCTS :: tlpUpsBatteryDetailCharge : 1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.4 ]. Possible values are 0: floating, 1: charging, 2: resting, 3: discharging, 4: normal, 5: standby.
Tripp Lite UPS Battery - Statisticstripplite_ups_battery_StatusTripp Lite UPS Battery StatusMonitors the Tripp Lite UPS Battery Status, which is the indication of the capacity remaining in the UPS system's batteries. [ TRIPPLITE-PRODUCTS :: tlpUpsBatteryStatus : 1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.1 ]. Possible Values are 1: unknown, 2: batteryNormal, 3: batteryLow, 4: batteryDepleted.
tripplite_ups_battery_EstimatedChargeRemainingTripp Lite UPS Battery Estimated Charge Remaining%Monitors the Tripp Lite UPS estimate of the battery charge remaining expressed as a percentage of full charge. [ TRIPPLITE-PRODUCTS :: tlpUpsEstimatedChargeRemaining : 1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.4 ]
Tripp Lite UPS Battery Pack - Detailstripplite_ups_battery_ConditionTripp Lite UPS Battery ConditionMonitors the Tripp Lite UPS Battery Condition. The condition of the battery. A bad battery should be replaced. [ TRIPPLITE-PRODUCTS :: tlpUpsBatteryPackDetailCondition : 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.1 ]. Possible values are 0: unknown, 1: good, 2: weak, 3: bad.
tripplite_ups_battery_AgeTripp Lite UPS Battery AgeDaysMonitors the age of the Tripp Lite UPS battery in tenths of years. This is equal to the current date minus tlpUpsBatteryPackDetailLastReplaceDate. [ TRIPPLITE-PRODUCTS :: tlpUpsBatteryPackDetailAge : 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.4 ]

Tripp Lite UPS Input

Description

This integration monitors key input phase statistics for Tripp Lite UPS devices, including:

  • Input Phase Frequency
  • Input Phase Voltage
  • Input Transformer Status These statistics denote the current status of the transformer, indicating whether it is reducing or boosting the input.

These metrics are collected via the following SNMP OIDs:

  • Input Phase Frequency: 1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.2
  • Input Phase Voltage: 1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.3
  • Input Transformer Status: 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.13

Validated Model: Tripp Lite SMART500RT1U
SysObjectOID: 1.3.6.1.4.1.850.1.1.1
Software Version: PowerAlert 20.2.0 (Build 922)

Prerequisites

None

Supported Metrics

Monitor NameMetric NameMetric Display NameUnitDescription
Tripp Lite UPS Input Phase - Statisticstripplite_ups_inputphase_FrequencyTripp Lite UPS Input Phase FrequencyHzMonitors the Tripp Lite UPS present input frequency for a given input line. [ TRIPPLITE-PRODUCTS :: tlpUpsInputPhaseFrequency : 1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.2 ].
tripplite_ups_inputphase_VoltageTripplite UPS Input Phase VoltageVMonitors the Tripplite UPS Input Phase Voltage which is the magnitude of the present input voltage for a given input line. [ TRIPPLITE-PRODUCTS :; tlpUpsInputPhaseVoltage : 1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.3 ]
Tripp Lite UPS Input Transformer Statustripplite_ups_input_TransformerStatusTripp Lite UPS Input Transformer StatusvMonitors the Tripp Lite UPS Input Transformer Status which Denotes the status of the transformer as to whether it is presently reducing or boosting the input. [ TRIPPLITE-PRODUCTS :: tlpUpsInputTransformerStatus : 1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.13 ]. Possible Values are 0: normal, 1: reducing, 2: boosting.

Tripp Lite UPS Output

Description

This integration monitors key output metrics for Tripp Lite UPS devices, including:

  • Output Source
  • Nominal Voltage
  • Frequency
  • Output Line Statistics, such as:
    • Voltage
    • Current
    • Active Power
    • Utilization

These metrics are collected via the following SNMP OIDs:

  • Output Source: 1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.1
  • Output Frequency: 1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.3
  • Output Line Voltage: 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.2
  • Output Line Current: 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.3
  • Output Line Active Power: 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.4
  • Output Line Utilization: 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.5

Validated Model: Tripp Lite SMART500RT1U
SysObjectOID: 1.3.6.1.4.1.850.1.1.1
Software Version: PowerAlert 20.2.0 (Build 922)

Supported Metrics

Monitor NameMetric NameMetric Display NameUnitDescription
Tripp Lite UPS Outputtripplite_ups_output_SourceTripp Lite UPS Output SourceHzMonitors the Tripp Lite UPS Output Source.The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the device has an open circuit breaker. Possible values are 0: unknown, 1: other, 2: none, 3: normal(3) 4: bypass, 5: battery, 6: boosting, 7: reducing, 8: second, 9: economy, 10: testing.
tripplite_ups_output_FrequencyTripp Lite UPS Output FrequencyHzMonitors the Tripplite UPS Output Frequency in Hertz. [ TRIPPLITE-PRODUCTS :: tlpUpsOutputFrequency : 1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.3 ]
Tripp Lite UPS Output Line - Statisticstripplite_ups_outpuline_VoltageTripp Lite UPS Output Line VoltageHzMonitors the Tripp Lite UPS Output Line Voltage which is the the magnitude of the present output voltage for a given output line.[ TRIPPLITE-PRODUCTS :: tlpUpsOutputLineVoltage : 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.2 ].
tripplite_ups_outpuline_CurrentTripp Lite UPS Output Line CurrentampsMonitors the Tripp Lite UPS Output Line Current. The output current, in hundredths of amps, for a given line. [ TRIPPLITE-PRODUCTS :: tlpUpsOutputLineCurrent : 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.3 ].
tripplite_ups_outpuline_ActivePowerTripp Lite UPS Output Line Active PowerWattsMonitors the Tripp Lite UPS Output Line Active Power.The present output true power. [ TRIPPLITE-PRODUCTS :: tlpUpsOutputLineActivePower : 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.4 ].
tripplite_ups_outpuline_UtilizationTripp Lite UPS Output Line Utilization%Monitors the Tripp Lite UPS Output Line Utilization.The percentage of the ups power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA. [ TRIPPLITE-PRODUCTS :: tlpUpsOutputLineUtilization : 1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.5 ].

Tripp Lite UPS Outlet

Description

Monitors important outlet-related metrics for Tripp Lite UPS devices, including:

  • Outlet State
  • Outlet Circuit
  • Outlet Phase

These metrics are collected via the following SNMP OIDs:

  • Outlet State: 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.4
  • Outlet Circuit: 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.16
  • Outlet Phase: 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.17

Validated Model: Tripp Lite SMART500RT1U
SysObjectOID: 1.3.6.1.4.1.850.1.1.1
Software Version: PowerAlert 20.2.0 (Build 922)

Prerequisites

None

Supported Metrics

Monitor NameMetric NameMetric Display NameUnitDescription
Tripp Lite UPS Outlet - Statisticstripplite_ups_outlet_StateTripp Lite UPS Outlet StateMonitors the Tripp Lite UPS current state of the outlet. [ PRODUCTS :: tlpUpsOutletState : 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.4 ]. Possible Values are 0: unknown, 1: off, 2: on.
tripplite_ups_outlet_PhaseTripplite UPS Outlet PhaseMonitors the Tripplite UPS Outlet Phase. Indicates on which phase or phases the given outlet is associated. [ TRIPPLITE-PRODUCTS :: tlpUpsOutletPhase : 1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.17 ]. Possible values are 0: unknown, 1: phase1, 2: phase2, 3: phase3, 4: phase1-2, 5: phase2-3, 6: phase3-1.

Tripp Lite UPS Battery Replace Days

Description

This monitor tracks the number of days since the Tripp Lite UPS system’s batteries were last replaced, as well as the number of days remaining until the next scheduled battery replacement.

The following metrics are monitored:

  • Last Replace Date: The number of days since the UPS batteries were last replaced.
  • Next Replace Date: The number of days until the next scheduled UPS battery replacement.

These metrics are collected via the following SNMP OIDs:

  • Last Replace Date: 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.5
  • Next Replace Date: 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.6

Validated Model: Tripp Lite SMART500RT1U
SysObjectOID: 1.3.6.1.4.1.850.1.1.1
Software Version: PowerAlert 20.2.0 (Build 922)

Prerequisites

None

Supported Metrics

Monitor NameMetric NameMetric Display NameUnitDescription
Tripp Lite UPS Battery Replace Daystripplite_ups_battery_LastReplaceDaysTripp Lite UPS Battery Last Replace DaysDaysThis monitor provides the number of days since the Tripp Lite UPS system's batteries were last replaced. [ TRIPPLITE-PRODUCTS :: upsBasicBatteryLastReplaceDate - 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.5 ].
tripplite_ups_battery_NextReplaceDaysTripp Lite UPS Battery Next Replace DaysDaysThis monitor provides the number of days until the Tripp Lite UPS system's batteries are scheduled to be replaced. [ TRIPPLITE-PRODUCTS :: tlpUpsBatteryPackDetailNextReplaceDate - 1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.6 ].