APC ATS(Automatic Transfer Switch)
Description
Template to monitor APC ATS(Automatic Transfer Switch) input frequency,output frequency,input phase voltage,power,current,output phase voltage,current,load,percent load,power,percent power,phase state and device hardware states. sysObjectID : 1.3.6.1.4.1.318.1.3.11,Model : AP7723,PF:v3.7.4 .
Prerequisites
The device should have support for PowerNet-MIB :: automaticTransferSwitch Table.
Supported Metric
Monitor Name | Metric Name | Metric Display Name | Unit | Description |
---|---|---|---|---|
APC ATS(Automatic Transfer Switch) - Input Frequency | apc.ats.input.frequency | Input Frequency | Hz | It monitors the input frequency of APC ATS(Automatic Transfer Switch) in hertz.[PowerNet-MIB::atsInputFrequency:1.3.6.1.4.1.318.1.1.8.5.3.2.1.4]. |
apc.ats.input.voltage | Input Voltage | v | It monitors the input voltage of APC ATS(Automatic Transfer Switch) in VAC(volts AC power). Here component name will be Input Identifier and InputPhase Identifier with dotted separation.[PowerNet-MIB::atsInputVoltage:1.3.6.1.4.1.318.1.1.8.5.3.3.1.3]. | |
apc.ats.input.current | Input Current | amps | It monitors the input current of APC ATS(Automatic Transfer Switch) in amperes. Here component name will be Input Identifier and InputPhase Identifier with dotted separation.[PowerNet-MIB::atsInputCurrent:1.3.6.1.4.1.318.1.1.8.5.3.3.1.6]. | |
apc.ats.input.power | Input Power | W | It monitors the input power of APC ATS(Automatic Transfer Switch) in Watts. Here component name will be Input Identifier and InputPhase Identifier with dotted separation.[PowerNet-MIB::atsInputPower:1.3.6.1.4.1.318.1.1.8.5.3.3.1.9]. | |
apc.ats.output.frequency | Ouput Frequency | Hz | It monitors the output frequency of APC ATS(Automatic Transfer Switch) in Hertz.[PowerNet-MIB::atsOutputFrequency:1.3.6.1.4.1.318.1.1.8.5.4.2.1.4]. | |
apc.ats.output.voltage | Output Voltage | v | It monitors the output voltage of APC ATS(Automatic Transfer Switch) in VAC(volts AC power). Here component name will be Output identifier and OutputPhase identifier with dotted separation.Possible values for OutputPhase identifier phase1(1),phase2(2),phase3(3),neutral(4).[PowerNet-MIB::atsOutputVoltage:1.3.6.1.4.1.318.1.1.8.5.4.3.1.3]. | |
apc.ats.output.current | Output Current | amps | It monitors the output current in 0.1 amperes drawn by the load on the ATS(Automatic Transfer Switch). Here component name will be Output identifier and OutputPhase identifier with dotted separation.Possible values for OutputPhase identifier phase1(1),phase2(2),phase3(3),neutral(4).[PowerNet-MIB::atsOutputCurrent:1.3.6.1.4.1.318.1.1.8.5.4.3.1.4]. | |
apc.ats.output.load | Output Load (VA) | It monitors the output load of APC ATS(Automatic Transfer Switch) in VA.Here component name will be Output identifier and OutputPhase identifier with dotted separation.Possible values for OutputPhase identifier phase1(1),phase2(2),phase3(3),neutral(4).[PowerNet-MIB::atsOutputLoad:1.3.6.1.4.1.318.1.1.8.5.4.3.1.7]. | ||
apc.ats.output.percent.load | Output Percent Load | % | It monitors the percentage of the ATS(Automatic Transfer Switch) load capacity in VA at redundancy @ (n + x) presently being used on this output phase. Here component name will be Output identifier and OutputPhase identifier with dotted separation.Possible values for OutputPhase identifier phase1(1),phase2(2),phase3(3),neutral(4).[PowerNet-MIB::atsOutputPercentLoad:1.3.6.1.4.1.318.1.1.8.5.4.3.1.10]. | |
apc.ats.output.power | Output Power (VA) | It monitors the output power of APC ATS(Automatic Transfer Switch) in VA. Here component name will be Output identifier and OutputPhase identifier with dotted separation.Possible values for OutputPhase identifier phase1(1),phase2(2),phase3(3),neutral(4).[PowerNet-MIB::atsOutputPower:1.3.6.1.4.1.318.1.1.8.5.4.3.1.13]. | ||
apc.ats.output.power.percent | Output Power Percent | % | It monitors the percentage of the ATS(Automatic Transfer Switch) power capacity in VA at redundancy @ (n + x) presently being used on this output phase. Here component name will be Output identifier and OutputPhase identifier with dotted separation.Possible values for OutputPhase identifier phase1(1),phase2(2),phase3(3),neutral(4).[PowerNet-MIB::atsOutputPercentPower:1.3.6.1.4.1.318.1.1.8.5.4.3.1.16]. | |
apc.ats.output.phase.state | Output Phase State | It monitors the phase load state of APC ATS (Automatic Transfer Switch). Possible values are 1: normal,2: lowload,3: nearoverload,4:overload(4).Here component name will be Output identifier and OutputPhase identifier with dotted separation.Possible values for OutputPhase identifier phase1(1),phase2(2),phase3(3),neutral(4).[PowerNet-MIB::atsOutputPhaseState:1.3.6.1.4.1.318.1.1.8.5.4.3.1.19]. | ||
apc.ats.comm.status | ATS Communication Status | Monitors the current communication status of the Automatic Transfer Switch (ATS). Possible values are 1- atsNeverDiscovered,2- atsCommEstablished,3- atsCommLost.[OIDs: 1.3.6.1.4.1.318.1.1.8.5.1.1.0]. | ||
apc.ats.redundancy.state | ATS Redundancy State | Monitors the current redundancy state of the ATS. atsRedundancyLost(1) indicates that the ATS is unable to switch over to the alternate power source if the current source fails. atsFullyRedundant(2) indicates that the ATS will switch over to the alternate power source if the current source fails.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.3.0]. | ||
apc.ats.over.current.state | ATS Over Current State | Monitors the output current state of the ATS. atsOverCurrent(1) indicates that the ATS has exceeded the output current threshold and will not allow a switch over to the alternate power source if the current source fails. atsCurrentOK(2) indicates that the output current is below the output current threshold.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.4.0]. | ||
apc.ats.powersupply5v.state | ATS 5V Power Supply State | Monitors the present state of the ATS 5V power supply. atsPowerSupplyFailure(1) indicates the 5V power supply has failed and that the ATS serial port Configuration Menu is not accessible . atsPowerSupplyOK(2) indicates that the ATS 5V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.5.0]. | ||
apc.ats.powersupply24v.state | ATS 24V Power Supply State | Monitors the present state of the ATS 24V power supply for Source A. atsPowerSupplyFailure(1) indicates the 24V power supply has failed and the ATS is unable to switch over to the alternate power source if the current source fails. atsPowerSupplyOK(2) indicates that the ATS 24V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.6.0]. | ||
apc.ats.sourceB.powersupply24v.state | ATS 24V Source B Power Supply State | Monitors the present state of the ATS 24V power supply for Source B. atsPowerSupplyFailure(1) indicates the 24V power supply has failed and the ATS is unable to switch over to the alternate power source if the current source fails. atsPowerSupplyOK(2) indicates that the ATS 24V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.7.0]. | ||
apc.ats.plus12v.powersupply.state | ATS +12V Power Supply State | Monitors the state of the ATS 12V power supply. atsPowerSupplyFailure(1) indicates the 12V power supply has failed and the ATS is unable to monitor the current sensors. atsPowerSupplyOK(2) indicates that the ATS 12V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.8.0]. | ||
apc.ats.minus12v.powersupply.state | ATS -12V Power Supply State | Monitors the present state of the ATS -12V power supply. atsPowerSupplyFailure(1) indicates the -12V power supply has failed and the ATS is unable to monitor the current sensors. atsPowerSupplyOK(2) indicates that the ATS -12V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.9.0]. | ||
apc.ats.switch.status | Automatic Transfer Switch (ATS) Status | Monitors the status of the ATS. Possible values are 1- fail,2- ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.10.0]. | ||
apc.ats.sourceA.status | ATS Source A Status | Monitors the status of the Source A. Possible values are 1- fail,2- ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.12.0]. | ||
apc.ats.sourceB.status | ATS Source B Status | Monitors the status of the Source B. Possible values are 1- fail,2- ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.13.0]. | ||
apc.ats.phasesync.status | ATS Phase Sync Status | Monitors the status of the phase synch. Possible values are 1- inSync,2- outOfSync.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.14.0]. | ||
apc.ats.vout.status | ATS Output Voltage Status | Monitors the output voltage status. Possible values are 1-fail,2-ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.15.0]. | ||
apc.ats.hardware.status | ATS Hardware Status | Monitors the status of display board hardware.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.16.0]. |
APC Hardware Status Monitors
Description
Monitors the APC hardware status such as APC External Environment Status,APC Integrated Environment Status,APC Environmental Management System Status,APC Rack Air Removal Unit Status,APC MasterSwitch Unit Status,APC MasterSwitch VM Unit Status,APC MasterSwitch Plus Unit Status,APC Automatic Transfer Switch(ATS) Status,APC NetworkAir FM System Status.
Prerequisites
No prerequisite
Supported Metric
Monitor Name | Metric Name | Metric Display Name | Unit | Description |
---|---|---|---|---|
APC Status Monitors | apc.ext.envmon.comm.status | External Environment Monitor Status | Monitors the communication status between the agent and the Environmental Monitor. Possible values are 1- noComm: Communication has never been established,2- comm: Communication has been established,3- commLost: Communication was established,but was lost.[OID: 1.3.6.1.4.1.318.1.1.10.1.3.1.0]. | |
apc.ats.comm.status | ATS Communication Status | Monitors the current communication status of the Automatic Transfer Switch (ATS). Possible values are 1- atsNeverDiscovered,2- atsCommEstablished,3- atsCommLost.[OIDs: 1.3.6.1.4.1.318.1.1.8.5.1.1.0]. | ||
apc.ats.redundancy.state | ATS Redundancy State | Monitors the current redundancy state of the ATS. atsRedundancyLost(1) indicates that the ATS is unable to switch over to the alternate power source if the current source fails. atsFullyRedundant(2) indicates that the ATS will switch over to the alternate power source if the current source fails.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.3.0]. | ||
apc.ats.over.current.state | ATS Over Current State | Monitors the output current state of the ATS. atsOverCurrent(1) indicates that the ATS has exceeded the output current threshold and will not allow a switch over to the alternate power source if the current source fails. atsCurrentOK(2) indicates that the output current is below the output current threshold.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.4.0]. | ||
apc.ats.powersupply5v.state | ATS 5V Power Supply State | Monitors the present state of the ATS 5V power supply. atsPowerSupplyFailure(1) indicates the 5V power supply has failed and that the ATS serial port Configuration Menu is not accessible . atsPowerSupplyOK(2) indicates that the ATS 5V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.5.0]. | ||
apc.ats.powersupply24v.state | ATS 24V Power Supply State | Monitors the present state of the ATS 24V power supply for Source A. atsPowerSupplyFailure(1) indicates the 24V power supply has failed and the ATS is unable to switch over to the alternate power source if the current source fails. atsPowerSupplyOK(2) indicates that the ATS 24V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.6.0]. | ||
apc.ats.sourceB.powersupply24v.state | ATS 24V Source B Power Supply State | Monitors the present state of the ATS 24V power supply for Source B. atsPowerSupplyFailure(1) indicates the 24V power supply has failed and the ATS is unable to switch over to the alternate power source if the current source fails. atsPowerSupplyOK(2) indicates that the ATS 24V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.7.0]. | ||
apc.ats.plus12v.powersupply.state | ATS +12V Power Supply State | Monitors the state of the ATS 12V power supply. atsPowerSupplyFailure(1) indicates the 12V power supply has failed and the ATS is unable to monitor the current sensors. atsPowerSupplyOK(2) indicates that the ATS 12V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.8.0]. | ||
apc.ats.minus12v.powersupply.state | ATS -12V Power Supply State | Monitors the present state of the ATS -12V power supply. atsPowerSupplyFailure(1) indicates the -12V power supply has failed and the ATS is unable to monitor the current sensors. atsPowerSupplyOK(2) indicates that the ATS -12V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.9.0]. | ||
apc.ats.switch.status | Automatic Transfer Switch (ATS) Status | Monitors the status of the ATS. Possible values are 1- fail,2- ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.10.0]. | ||
apc.ats.sourceA.status | ATS Source A Status | Monitors the status of the Source A. Possible values are 1- fail,2- ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.12.0]. | ||
apc.ats.sourceB.status | ATS Source B Status | Monitors the status of the Source B. Possible values are 1- fail,2- ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.13.0]. | ||
apc.ats.phasesync.status | ATS Phase Sync Status | Monitors the status of the phase synch. Possible values are 1- inSync,2- outOfSync.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.14.0]. | ||
apc.ats.vout.status | ATS Output Voltage Status | Monitors the output voltage status. Possible values are 1-fail,2-ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.15.0]. | ||
apc.ats.hardware.status | ATS Hardware Status | Monitors the status of display board hardware.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.16.0]. | ||
apc.airfmsys.present.status | Air FM System Present Status | Monitors the present mode of the System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. Possible values are 1- notApplicable,2- reserved1,3- reserved2,4- onLine,5- idle,6- loadShare,7- failed,8- offLine.[OID: 1.3.6.1.4.1.318.1.1.13.1.4.1.2.0]. | ||
APC Air FM System Input Status | apc.airfmsys.input.status | Air FM System Input Status | Monitors the state of this contact: Open(1) or Closed(2). A violation will occur when this relay is not in its normal state.[OIDs: 1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.3,1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.3]. | |
APC Air FM System Output Status | apc.airfmsys.ouput.status | Air FM System Output Status | Monitors the state of this contact: Open(1) or Closed(2). A violation will occur when this relay is not in its normal state.[OIDs: 1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.2,1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.3]. | |
APC EMS Alarm Device State | apc.ems.alarm.device.state | EMS Alarm Device State | Monitors the alarm device state. Possible values are 1- alarmDeviceOnEMS: device is active,2- alarmDeviceOffEMS: device is inactive,3- alarmDeviceNotInstalledEMS: device is not installed.[OIDs: 1.3.6.1.4.1.318.1.1.10.3.17.1.1.2,1.3.6.1.4.1.318.1.1.10.3.17.1.1.3]. | |
APC EMS Communication Status | apc.ems.comm.status | EMS Communication Status | Monitors the communication status between the agent and the Environment Management System (EMS). Possible values are 1- noComm: Communication has never been established,2- comm: Communication has been established,3- commLost: Communication was established,but was lost.[OIDs: 1.3.6.1.4.1.318.1.1.10.3.12.1,1.3.6.1.4.1.318.1.1.10.3.12.2]. | |
APC EMS Input Contact State | apc.ems.input.contact.state | EMS Input Contact State | Monitors the state of the input contact. Possible values are 1- contactClosedEMS: input contact is closed,2- contactOpenEMS : input contact state is open.[OIDs: 1.3.6.1.4.1.318.1.1.10.3.14.1.1.2,1.3.6.1.4.1.318.1.1.10.3.14.1.1.3]. | |
APC EMS Outlet State | apc.ems.outlet.state | EMS Outlet State | Monitors the state of the outlet. Possible values are 1- outletOnEMS: outlet is on,2- outletOffEMS: outlet is off.[OIDs: 1.3.6.1.4.1.318.1.1.10.3.16.1.1.2,1.3.6.1.4.1.318.1.1.10.3.16.1.1.3]. | |
APC EMS Probe Communication Status | apc.ems.probe.comm.status | EMS Probe Communication Status | Monitors the state of communications to the probe. Possible values are 1- commsNeverDiscovered: indicates there has never been communications with this device,2- commsEstablished: indicates communication is normal and active with this device,3- commsLost: indicates communication had been established,but is no longer.[OIDs: 1.3.6.1.4.1.318.1.1.10.3.13.1.1.2,1.3.6.1.4.1.318.1.1.10.3.13.1.1.10]. | |
APC EMS Relay State | apc.ems.outrelay.status | EMS Output Relay State | Monitors the state of the output relay. Possible values are 1- relayClosedEMS: output relay is closed,2- relayOpenEMS : output relay is open.[OIDs: 1.3.6.1.4.1.318.1.1.10.3.15.1.1.2,1.3.6.1.4.1.318.1.1.10.3.15.1.1.3]. | |
APC EMS Sensor State | apc.ems.sensor.state | EMS Sensor State | Monitors the sensor state. Possible values are 1- sensorFaultedEMS: sensor is faulted,2- sensorOKEMS: sensor is not faulted,3- sensorNotInstalledEMS: sensor is not installed.[OIDs: 1.3.6.1.4.1.318.1.1.10.3.18.1.1.3,1.3.6.1.4.1.318.1.1.10.3.18.1.1.4]. | |
APC External Environment Probe Status | apc.ext.envmon.probe.status | External Environment Probe Status | Monitors the connected status of the probe,either disconnected(1) or connected(2).[OIDs: 1.3.6.1.4.1.318.1.1.10.1.3.3.1.3,1.3.6.1.4.1.318.1.1.10.1.3.3.1.2]. | |
APC Integrated Environment Probe Status | apc.integrated.envmon.probe.status | Integrated Environment Probe Status | Monitors the connected status of the probe,either disconnected(1) or connected(2).[OIDs: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.2,1.3.6.1.4.1.318.1.1.10.2.3.2.1.3]. | |
APC Integrated Environment Relay Status | apc.integrated.envmon.outrelay.status | Integrated Environment Output Relay Status | Monitors the status of the output relay,either faultState(1) or normalState(2).[OIDs: 1.3.6.1.4.1.318.1.1.10.2.3.7.1.2,1.3.6.1.4.1.318.1.1.10.2.3.7.1.3]. | |
APC MasterSwitch Plus Outlet State | apc.masterswitchplus.outlet.state | MasterSwitch Plus Outlet State | Monitors the outlet state. If the outlet is on,the outletStatusMSPOn (1) value will be returned. If the outlet is off,the outletStatusMSPOff (2) value will be returned.[OIDs: 1.3.6.1.4.1.318.1.1.6.7.1.1.2,1.3.6.1.4.1.318.1.1.6.7.1.1.4,1.3.6.1.4.1.318.1.1.6.7.1.1.5]. | |
APC MasterSwitch VM Current Load | apc.masterswitchvm.current.load | MasterSwitch VM Current Load | % | Monitors the total amount of power being consumed by the load. It is represented as a percentage of full load.[OIDs: 1.3.6.1.4.1.318.1.1.5.4.2.1.2,1.3.6.1.4.1.318.1.1.5.4.2.1.6]. |
APC MasterSwitch VM Outlet State | apc.masterswitchvm.outlet.state | MasterSwitch VM Outlet State | Monitors the outlet state. If the outlet is on,the outletStatusOnVM (1) value will be returned. If the outlet is off,the outletStatusOffVM (2) value will be returned.[OIDs: 1.3.6.1.4.1.318.1.1.5.7.1.1.2,1.3.6.1.4.1.318.1.1.5.7.1.1.4,1.3.6.1.4.1.318.1.1.5.7.1.1.5]. | |
APC Rack Air Removal Unit Status | apc.aru.alarm.status | ARU Alarm Status | Monitors the current alarm state of the Air Removal Unit (ARU). If the state of the ARU is unknown,this variable is set to 'UNKNOWN'. It is an ASCII string containing the 8 flags. The flags are defined as follows: Flag 1: Fan Fail 1 Flag 2: Fan Fail 2 Flag 3: Fan Fail 3 Flag 4: Smoke (if ARU is equipped with smoke detector) Flag 5: High Temp (Out of Thermal Control) Flag 6: Over Temp (Exhaust Temp. Exceeds Override Setpoint) Flag 7: Fan Fail 4 (Gen 2 ARU only) Flag 8: Reserved.[OIDs: 1.3.6.1.4.1.318.1.1.14.3.3.1.2,1.3.6.1.4.1.318.1.1.14.3.3.1.10]. | |
apc.aru.comm.status | ARU Communication Status | Monitors the state of communications to the device. Possible values are 1- commsNeverDiscovered: there has never been communications with this device,2- commsEstablished: communication is normal and active with this device,3- commsLost: communication had been established,but is no device.[OIDs: 1.3.6.1.4.1.318.1.1.14.3.3.1.2,1.3.6.1.4.1.318.1.1.14.3.3.1.2]. |
APC NetShelter Advanced Rack PDU Hardware Monitors
Description
Template to monitor the APC NetShelter Advanced Rack PDU Hardware Statistics like Circuit Breaker,External Sensor,Outlet Metered Status,Outlet Switched Control State,Outlet Switched Current Rating,Outlet Switched StartUp State,Outlet Switched State,Smart Cabinet Control,Input Phase,Unit Power Share,Voltage,Frequency,Current,Load State,Active Power and Energy.[PowerNet-MIB :: pduCircuitBreakerStatusLoadState : 1.3.6.1.4.1.318.1.1.32.4.4.1.4,pduCircuitBreakerStatusCurrent : 1.3.6.1.4.1.318.1.1.32.4.4.1.5,pduExternalSensorStatusCommStatus : 1.3.6.1.4.1.318.1.1.32.6.4.1.3,pduExternalSensorStatusState : 1.3.6.1.4.1.318.1.1.32.6.4.1.4,pduOutletMeteredStatusLoadState : 1.3.6.1.4.1.318.1.1.32.5.9.1.4,pduOutletMeteredStatusCurrent : 1.3.6.1.4.1.318.1.1.32.5.9.1.5,pduOutletMeteredStatusActivePower : 1.3.6.1.4.1.318.1.1.32.5.9.1.6,pduOutletSwitchedControlCommand : 1.3.6.1.4.1.318.1.1.32.5.5.1.4,pduOutletSwitchedPropertiesCurrentRating : 1.3.6.1.4.1.318.1.1.32.5.3.1.6,pduOutletSwitchedStateOnStartup : 1.3.6.1.4.1.318.1.1.32.5.2.1.3,pduOutletSwitchedStatusState : 1.3.6.1.4.1.318.1.1.32.5.4.1.4,pduUnitSmartCabinetControlUserName : 1.3.6.1.4.1.318.1.1.32.7.3.1.0,pduUnitSmartCabinetControlCardID : 1.3.6.1.4.1.318.1.1.32.7.3.2.0,pduUnitSmartCabinetControlDoor : 1.3.6.1.4.1.318.1.1.32.7.3.4.0,pduUnitSmartCabinetColdAisleLockStatus : 1.3.6.1.4.1.318.1.1.32.7.3.6.0,pduUnitSmartCabinetHotAisleLockStatus : 1.3.6.1.4.1.318.1.1.32.7.3.7.0,pduInputPhaseStatusCurrentState : 1.3.6.1.4.1.318.1.1.32.3.4.1.3,pduInputPhaseStatusVoltageState : 1.3.6.1.4.1.318.1.1.32.3.4.1.4,pduInputPhaseStatusCurrent: 1.3.6.1.4.1.318.1.1.32.3.4.1.5,pduInputPhaseStatusVoltage : 1.3.6.1.4.1.318.1.1.32.3.4.1.6,pduInputPhaseStatusActivePower : 1.3.6.1.4.1.318.1.1.32.3.4.1.7,pduUnitPsSupportUpstreamStatus : 1.3.6.1.4.1.318.1.1.32.2.4.1.2,pduUnitPsSupportDownstreamStatus : 1.3.6.1.4.1.318.1.1.32.2.4.1.3,pduUnitPsOptMode : 1.3.6.1.4.1.318.1.1.32.2.4.1.4,pduUnitPropertiesRatedVoltage : 1.3.6.1.4.1.318.1.1.32.2.3.1.10,pduUnitPropertiesRatedMaxCurrent : 1.3.6.1.4.1.318.1.1.32.2.3.1.11,pduUnitPropertiesRatedFrequency : 1.3.6.1.4.1.318.1.1.32.2.3.1.12,pduUnitPropertiesRatedPower : 1.3.6.1.4.1.318.1.1.32.2.3.1.13,pduUnitStatusLoadState : 1.3.6.1.4.1.318.1.1.32.2.4.1.3,pduUnitStatusActivePower : 1.3.6.1.4.1.318.1.1.32.2.4.1.4,pduUnitStatusEnergy : 1.3.6.1.4.1.318.1.1.32.2.4.1.9]
Prerequisites
The Device Should have Support for the PowerNet-MIB
Supported Metric
Monitor Name | Metric Name | Metric Display Name | Unit | Description |
---|---|---|---|---|
APC cPDU - Circuit Breaker | apc_cPDU_CircuitBreaker_LoadState | APC cPDU Circuit Breaker Load status | Monitors the APC PDU Circuit Breaker present Load Status. Possible values are 1- upperCritical,2- upperWarning,3- lowerWarning,4- lowerCritical,5- normal,6- off.[PowerNet-MIB :: pduUnitStatusLoadState : 1.3.6.1.4.1.318.1.1.32.4.4.1.4] | |
apc_cPDU_CircuitBreaker_Current | APC cPDU Circuit Breaker Current | amps | Monitors the PDU Circuit Breaker Current in hundredths of Amps.[PowerNet-MIB :: pduCircuitBreakerStatusCurrent : 1.3.6.1.4.1.318.1.1.32.4.4.1.5] | |
APC cPDU - External Sensor | apc_cPDU_ExternalSensor_CommStatus | APC cPDU Sensor Communication Status | Monitors the Communications Status of the Sensor.Possible Values are 0- notInstalled,1- commsOk,2- commsLost.[PowerNet-MIB :: pduExternalSensorStatusCommStatus : 1.3.6.1.4.1.318.1.1.32.6.4.1.3] | |
apc_cPDU_ExternalSensor_State | APC cPDU Sensor Current Status | Monitors the External Sensor Current Status. Possible Value are 0- notPresent,1- alarmed,2- normal,3- belowLowerCritical,4- belowLowerWarning,5- aboveUpperWarning,6- aboveUpperCritical.[PowerNet-MIB :: pduExternalSensorStatusState : 1.3.6.1.4.1.318.1.1.32.6.4.1.4] | ||
APC cPDU - Outlet Metered Status | apc_cPDU_OutletMetered_LoadState | APC cPDU Outlet Metered Load Status | Monitors the Present Load Status of the PDU Metered Outlet.Possible values are 1- upperCritical,2- upperWarning,3- lowerWarning,4- lowerCritical,5- normal.[PowerNet-MIB :: pduOutletMeteredStatusLoadState : 1.3.6.1.4.1.318.1.1.32.5.9.1.4] | |
apc_cPDU_OutletMetered_ActivePower | APC cPDU Outlet Metered Power | W | Monitors the APC PDU Power in Watts,of the Load on the PDU outlet.[PowerNet-MIB :: pduOutletMeteredStatusActivePower : 1.3.6.1.4.1.318.1.1.32.5.9.1.6] | |
apc_cPDU_OutletMetered_Current | APC cPDU Outlet Metered Current | amps | Monitors the APC PDU Current,in hundredths of Amps,on the PDU outlet.[PowerNet-MIB :: pduOutletMeteredStatusCurrent : 1.3.6.1.4.1.318.1.1.32.5.9.1.5] | |
APC cPDU - Outlet Switched Control State | apc_cPDU_OutletSwitched_ControlCommand | APC cPDU Switched Outlet Control State | Monitors the APC PDU Switched Outlet Control State.Possible Values are 1- immediateOff,2-immediateOn,3- delayedOff,4- delayedOn,5-immediateReboot,6- delayedReboot(6) 7- outletUnknown.[PowerNet-MIB :: pduOutletSwitchedControlCommand : 1.3.6.1.4.1.318.1.1.32.5.5.1.4] | |
APC cPDU - Outlet Switched Current Rating | apc_cPDU_OutletSwitched_CurrentRating | APC cPDU Outlet Switched Current Rating | amps | Monitors the Current Rating of Outlet in hundreths of Ampere.[PowerNet-MIB :: pduOutletSwitchedPropertiesCurrentRating : 1.3.6.1.4.1.318.1.1.32.5.3.1.6] |
APC cPDU - Outlet Switched StartUp State | apc_cPDU_OutletSwitched_StateOnStartup | APC cPDU Switched Outlet State | Monitors the APC PDU Switched Outlet State on device startup.Possible Values are 0- off,1- on,2- lastKnownState.[PowerNet-MIB :: pduOutletSwitchedStateOnStartup : 1.3.6.1.4.1.318.1.1.32.5.2.1.3] | |
APC cPDU - Outlet Switched State | apc_cPDU_OutletSwitched_State | APC cPDU Switched Outlet Switch State | Monitors the APC PDU present switch state of switched outlet.Possible Values are 1- on,0-off.[PowerNet-MIB :: pduOutletSwitchedStatusState : 1.3.6.1.4.1.318.1.1.32.5.4.1.4] | |
APC cPDU - Smart Cabinet Control | apc_cPDU_SmartCabinet_UserName | APC cPDU Smart Cabinet UserName | Monitors the PDU Smart Cabinet UserName.[PowerNet-MIB :: pduUnitSmartCabinetControlUserName : 1.3.6.1.4.1.318.1.1.32.7.3.0] | |
apc_cPDU_SmartCabinet_CardID | APC cPDU Smart Cabinet Card ID | Monitors the APC PDU Smart Cabinet Card ID.[PowerNet-MIB :: pduUnitSmartCabinetControlCardID : 1.3.6.1.4.1.318.1.1.32.7.3.2.0] | ||
apc_cPDU_SmartCabinet_Door | APC cPDU Smart Cabinet Door | Monitors the APC PDU Aisle of Smart Cabinet.[PowerNet-MIB :: pduUnitSmartCabinetControlDoor : 1.3.6.1.4.1.318.1.1.32.7.3.4.0] | ||
apc_cPDU_SmartCabinet_ColdAisleLockStatus | APC cPDU Smart Cabinet Cold Aisle Lock State | Monitors the APC PDU Smart Cabinet ColdAisle lock state.[PowerNet-MIB :: pduUnitSmartCabinetColdAisleLockStatus : 1.3.6.1.4.1.318.1.1.32.7.3.6.0] | ||
apc_cPDU_SmartCabinet_HotAisleLockStatus | APC cPDU Smart Cabinet Hot Aisle Lock State | Monitors the APC PDU Smart Cabinet HotAisle lock state.[PowerNet-MIB :: pduUnitSmartCabinetHotAisleLockStatus: 1.3.6.1.4.1.318.1.1.32.7.3.7.0] | ||
APC cPDU - Input Phase | apc_cPDU_InputPhase_CurrentState | APC cPDU Input Phase Current State | Monitors the APC PDU present current status.Possible values are 1- upperCritical,2- upperWarning,3- lowerWarning,4- lowerCritical,5- normal.[PowerNet-MIB :: pduInputPhaseStatusCurrentState : 1.3.6.1.4.1.318.1.1.32.3.4.1.3] | |
apc_cPDU_InputPhase_VoltageState | APC cPDU Input Phase Voltage State | Monitors the APC PDU present voltage status of the PDU Input Phase.Possible values are 1- upperCritical,2- upperWarning,3- lowerWarning,4- lowerCritical,5- normal.[PowerNet-MIB :: pduOutletSwitchedStatusState : 1.3.6.1.4.1.318.1.1.32.5.4.1.4] | ||
apc_cPDU_InputPhase_VoltageStatus | APC cPDU Input Phase Voltage Status | v | Monitors the APC PDU Input Phase voltage,in Volts(V)[PowerNet-MIB :: pduInputPhaseStatusVoltage : 1.3.6.1.4.1.318.1.1.32.3.4.1.6] | |
apc_cPDU_InputPhase_ActivePower | APC cPDU Input Phase Power | W | Monitors the APC PDU present power consumption,in Watts.[PowerNet-MIB :: pduInputPhaseStatusActivePower : 1.3.6.1.4.1.318.1.1.32.3.4.1.7] | |
apc_cPDU_InputPhase_CurrentStatus | APC cPDU Input phase Current | amps | Monitors the PDU Input phase current in hundredths of Amps.[PowerNet-MIB :: pduInputPhaseStatusCurrent : 1.3.6.1.4.1.318.1.1.32.3.4.1.5] | |
APC cPDU - Unit Power Share | apc_cPDU_PowerShare_UpstreamStatus | APC cPDU Power Share Upstream Status | Monitors the PDU Power Share UpstreamStatus. Possible Values are 0- notAvailable,1- available.[PowerNet-MIB :: pduUnitPsSupportUpstreamStatus : 1.3.6.1.4.1.318.1.1.32.2.5.1.2] | |
apc_cPDU_PowerShare_DownstreamStatus | APC cPDU Power Share DownstreamStatus | Monitors the Power share support status on downstream PDU. Possible Values are 0- notAvailable,1- available.[PowerNet-MIB :: pduUnitPsSupportDownstreamStatus : 1.3.6.1.4.1.318.1.1.32.2.5.1.3] | ||
apc_cPDU_PowerShare_OptMode | APC cPDU Power Operating Mode | Monitors the PDU Operating power status. Possible Values are 0- backupPower,1- mainPower.[PowerNet-MIB :: pduUnitPsOptMode : 1.3.6.1.4.1.318.1.1.32.2.5.1.4] | ||
APC cPDU - Unit Properties | apc_cPDU_RatedVoltage | APC cPDU Voltage Rating | v | Monitors the APC PDU Voltage Rating in Volts.[PowerNet-MIB :: pduUnitPropertiesRatedVoltage : 1.3.6.1.4.1.318.1.1.32.2.3.1.10] |
apc_cPDU_RatedMaxCurrent | APC cPDU Current Rating | amps | Monitors the APC PDU Current Rating in Amps.[PowerNet-MIB :: pduUnitPropertiesRatedMaxCurrent : 1.3.6.1.4.1.318.1.1.32.2.3.1.11] | |
apc_cPDU_RatedFrequency | APC cPDU Frequency Rating | Hz | Monitors the APC PDU Frequency Rating in Hz.[PowerNet-MIB :: pduUnitPropertiesRatedFrequency : 1.3.6.1.4.1.318.1.1.32.2.3.1.12] | |
apc_cPDU_RatedPower | APC cPDU Power Rating | W | Monitors the APC PDU Power Rating in (VoltAmps).[PowerNet-MIB :: pduUnitPropertiesRatedPower : 1.3.6.1.4.1.318.1.1.32.2.3.1.13] | |
APC cPDU - Unit Status | apc_cPDU_LoadState | APC cPDU Load Status | Monitors the present Load Status of the APC PDU based on Active Power.Possible values are 1- upperCritical,2- upperWarning,3- lowerWarning,4- lowerCritical,5- normal.[PowerNet-MIB :: pduUnitStatusLoadState : 1.3.6.1.4.1.318.1.1.32.2.4.1.3] | |
apc_cPDU_ActivePower | APC cPDU Active Power Consumed | W | Monitors the power consumption,in Watts(W).[PowerNet-MIB :: pduUnitStatusActivePower : 1.3.6.1.4.1.318.1.1.32.2.4.1.4] | |
apc_cPDU_Energy | APC cPDU Energy Consumed | W | Monitors the APC PDU Total Energy Consumed,in tenths of Kilowatt-Hours(kWh),of the PDU over its lifetime.[PowerNet-MIB :: pduUnitStatusEnergy : 1.3.6.1.4.1.318.1.1.32.2.4.1.9] |
APC Rack PDU Status - G2
Description
Template for Power Distribution unit. Performs application monitoring on PDU bank state,load state,master switch state,outlet state etc,.
Prerequisites
No prerequisite
Supported Metric
Monitor Name | Metric Name | Metric Display Name | Unit | Description |
---|---|---|---|---|
APC PDU Load State | pdu.load.state | PDU Load State | Indicates the phase/bank load status. phaseLoadNormal(1) indicates that the phase is operating properly within the rPDULoadConfigLowLoadThreshold and rPDULoadConfigNearOverloadThreshold OID values. phaseLoadLow(2) indicates that the phase load has dropped below the rPDULoadConfigLowLoadThreshold OID value. phaseLoadNearOverload(3) indicates that the phase load is greater than or equal to the rPDULoadConfigNearOverloadThreshold OID value. phaseLoadOverload(4) indicates that the phase load is greater than or equal to the rPDULoadConfigOverloadThreshold OID value.[OID: 1.3.6.1.4.1.318.1.1.12.2.3.1.1.3]. | |
pdu.current.load | PDU Current Load | amps | APC PDU phase/bank current load in amps.[OIDs: 1.3.6.1.4.1.318.1.1.12.2.3.1.1.2]. | |
APC PDU Outlet State | pdu.outlet.state | PDU Outlet State | Provides the name and the state of the outlet. Possible values are 1-Outlet On,2- Outlet Off,3- Outlet Reboot,4- Outlet Unknown,5- Outlet On With Delay,6- Outlet Off With Delay,7- Outlet Reboot With Delay.[OID: 1.3.6.1.4.1.318.1.1.4.4.2.1.3]. | |
APC PDU Outlet Statistics | pdu.controlled.outlets | PDU Controlled Outlets | The number of controlled outlets on this Switched Rack PDU.[OID: 1.3.6.1.4.1.318.1.1.12.3.1.3.0]. | |
pdu.total.outlets | PDU Total Outlets | The total number of outlets on this Rack PDU.[OID: 1.3.6.1.4.1.318.1.1.12.3.1.4.0]. | ||
pdu.monitored.outlets | PDU Monitored Outlets | Represents the PDU Outlets Monitored.[OID: 1.3.6.1.4.1.318.1.1.12.3.1.5.0]. | ||
pdu.power.supply.status | PDU Power Supply Status | Indicates the PowerSupply alarm. Possible values are 1- All Available Power Supplies OK,2- Power Supply One Failed,3- Power Supply Two Failed,4- Power Supply One and Two Failed.[OID: 1.3.6.1.4.1.318.1.1.12.4.1.3.0]. | ||
APC PDU Bank State | pdu.bank.state | PDU Bank State | Provides the index to the RACK PDU Bank entry and the bank load state. Possible values are 1- Bank Load Normal,2- Bank Load Low,3- Bank Load Never Overlaod,4- Bank Load Overload.[OID: 1.3.6.1.4.1.318.1.1.12.5.2.1.3]. | |
APC PDU Load Bank Configuration Alarm | pdu.loadbank.config.alarm | PDU Load Bank Configuration Alarm | Provides the current bank load alarm state. Possible alarm status values are 1- No Load Alarm,2- Under Current Alarm,3- Near Over Current Alarm,4- Over Current Alarm.[OID: 1.3.6.1.4.1.318.1.1.12.2.4.1.1.5]. | |
APC PDU Master Switch State | pdu.master.switch.state | PDU Master Switch State | Monitors the status of all outlets.[OID: 1.3.6.1.4.1.318.1.1.4.2.2.0]. |
APC UPS Battery Last Replace And Manufacture Days
Description
This template provides the number of days since the UPS system’s batteries were last replaced and UPS was manufactured.[PowerNet-MIB :: upsBasicBatteryLastReplaceDate : 1.3.6.1.4.1.318.1.1.1.2.1.3.0,upsAdvIdentDateOfManufacture : 1.3.6.1.4.1.318.1.1.1.1.2.2.0]
Prerequisites
NULL
Supported Metric
Monitor Name | Metric Name | Metric Display Name | Unit | Description |
---|---|---|---|---|
APC UPS Battery Last Replace And Manufacture Days | apc_ups_BatteryLastReplaceDays | APC UPS Battery Last Replace Days | Days | Monitor provides the number of days since the UPS system's batteries were last replaced.[PowerNet-MIB :: upsBasicBatteryLastReplaceDate : 1.3.6.1.4.1.318.1.1.1.2.1.3.0] |
apc_ups_ManufactureDays | APC UPS Manufacture Days | Days | This monitor provides the number of days since the UPS was manufactured.[PowerNet-MIB :: upsAdvIdentDateOfManufacture : 1.3.6.1.4.1.318.1.1.1.1.2.2.0] |
APC UPS Status Check - G2
Description
Template for monitoring APC UPS. Monitors battery capacity,battery status,run time remaining,temperature,input line voltage,output line voltage,etc. Tested on APC Web/SNMP Management Card. System Object Id: 1.3.6.1.4.1.318.1.3.27.
Prerequisites
No prerequisite
Supported Metric
Monitor Name | Metric Name | Metric Display Name | Unit | Description |
---|---|---|---|---|
APC UPS Monitors | ups.battery.status | UPS Battery status | Indicates the status of the UPS batteries. Possible status values are 1 - Unknown,2 - Battery Normal,3 - Battery Low.[OID: 1.3.6.1.4.1.318.1.1.1.2.1.1]. | |
ups.no.of.batter.packs.bad | UPS No Of Bad Battery Packs | The number of external battery packs connected to the UPS that are defective.[OID: 1.3.6.1.4.1.318.1.1.1.2.2.6]. | ||
ups.battery.capacity | UPS Battery Capacity | % | The remaining battery capacity expressed in percent of full capacity. Alert is generated when the battery capacity is less than 99%.[OID: 1.3.6.1.4.1.318.1.1.1.2.2.1.0]. | |
ups.battery.replace.indicator | UPS Battery Replace Indicator | Indicates whether the UPS batteries need replacing. Possible values are 1 - No Battery Needs Replacing,2 - Battery Needs Replacing.[OID: 1.3.6.1.4.1.318.1.1.1.2.2.4]. | ||
ups.battery.runtime.remaining | UPS Battery Runtime Remaining | s | Indicates the UPS battery run time remaining before battery exhaustion.[OID: 1.3.6.1.4.1.318.1.1.1.2.2.3.0]. | |
ups.battery.temperature | UPS Battery Temperature | Celsius | The current internal UPS temperature expressed in Celsius.[OID: 1.3.6.1.4.1.318.1.1.1.2.2.2.0]. | |
ups.inputline.voltage | UPS Input Line Voltage | v | Indicates the current utility line voltage in VAC.[OID: 1.3.6.1.4.1.318.1.1.1.3.2.1.0]. | |
ups.frequency.output | UPS Output Frequency | Hz | Indicates the current output frequency of the UPS system in Hz.[OID: 1.3.6.1.4.1.318.1.1.1.4.2.2]. | |
ups.load.output | UPS Output Load | % | Indicates the current UPS load expressed in percent of rated capacity.[OID: 1.3.6.1.4.1.318.1.1.1.4.2.3]. | |
ups.status.output | UPS Output Status | Indicates that the UPS is not supplying line voltage to any attached devices. Possible status values are 1 -Unknown,2 - On Line,3 - On Battery,4 - On Smart boost,5 - Timed Sleeping,6 - Software Bypass,7 - Off,8 - Rebooting,9 - Switched Bypass,10-hardwareFailureBypass 11-SleepingUntilPowerReturn 12-onSmartTrim,13-ecoMode,14-hotStandby,15-onBatteryTest.[OID: 1.3.6.1.4.1.318.1.1.1.4.1.1]. | ||
ups.voltage.output | UPS Output Voltage | v | Indicates the output voltage of the UPS system in VAC.[OID: 1.3.6.1.4.1.318.1.1.1.4.2.1]. | |
ups.battery.time | UPS Time On Battery | s | The elapsed time since the UPS has switched to battery power. Alert is generated when the time on battery is greater than 0 seconds.[OID: 1.3.6.1.4.1.318.1.1.1.2.1.2]. |