APC ATS(Automatic Transfer Switch)

Description

Template to monitor APC ATS(Automatic Transfer Switch) input frequency,output frequency,input phase voltage,power,current,output phase voltage,current,load,percent load,power,percent power,phase state and device hardware states. sysObjectID : 1.3.6.1.4.1.318.1.3.11,Model : AP7723,PF:v3.7.4 .

Prerequisites

The device should have support for PowerNet-MIB :: automaticTransferSwitch Table.

Supported Metric

Monitor NameMetric NameMetric Display NameUnitDescription
APC ATS(Automatic Transfer Switch) - Input Frequencyapc.ats.input.frequencyInput FrequencyHzIt monitors the input frequency of APC ATS(Automatic Transfer Switch) in hertz.[PowerNet-MIB::atsInputFrequency:1.3.6.1.4.1.318.1.1.8.5.3.2.1.4].
apc.ats.input.voltageInput VoltagevIt monitors the input voltage of APC ATS(Automatic Transfer Switch) in VAC(volts AC power). Here component name will be Input Identifier and InputPhase Identifier with dotted separation.[PowerNet-MIB::atsInputVoltage:1.3.6.1.4.1.318.1.1.8.5.3.3.1.3].
apc.ats.input.currentInput CurrentampsIt monitors the input current of APC ATS(Automatic Transfer Switch) in amperes. Here component name will be Input Identifier and InputPhase Identifier with dotted separation.[PowerNet-MIB::atsInputCurrent:1.3.6.1.4.1.318.1.1.8.5.3.3.1.6].
apc.ats.input.powerInput PowerWIt monitors the input power of APC ATS(Automatic Transfer Switch) in Watts. Here component name will be Input Identifier and InputPhase Identifier with dotted separation.[PowerNet-MIB::atsInputPower:1.3.6.1.4.1.318.1.1.8.5.3.3.1.9].
apc.ats.output.frequencyOuput FrequencyHzIt monitors the output frequency of APC ATS(Automatic Transfer Switch) in Hertz.[PowerNet-MIB::atsOutputFrequency:1.3.6.1.4.1.318.1.1.8.5.4.2.1.4].
apc.ats.output.voltageOutput VoltagevIt monitors the output voltage of APC ATS(Automatic Transfer Switch) in VAC(volts AC power). Here component name will be Output identifier and OutputPhase identifier with dotted separation.Possible values for OutputPhase identifier phase1(1),phase2(2),phase3(3),neutral(4).[PowerNet-MIB::atsOutputVoltage:1.3.6.1.4.1.318.1.1.8.5.4.3.1.3].
apc.ats.output.currentOutput CurrentampsIt monitors the output current in 0.1 amperes drawn by the load on the ATS(Automatic Transfer Switch). Here component name will be Output identifier and OutputPhase identifier with dotted separation.Possible values for OutputPhase identifier phase1(1),phase2(2),phase3(3),neutral(4).[PowerNet-MIB::atsOutputCurrent:1.3.6.1.4.1.318.1.1.8.5.4.3.1.4].
apc.ats.output.loadOutput Load (VA)It monitors the output load of APC ATS(Automatic Transfer Switch) in VA.Here component name will be Output identifier and OutputPhase identifier with dotted separation.Possible values for OutputPhase identifier phase1(1),phase2(2),phase3(3),neutral(4).[PowerNet-MIB::atsOutputLoad:1.3.6.1.4.1.318.1.1.8.5.4.3.1.7].
apc.ats.output.percent.loadOutput Percent Load%It monitors the percentage of the ATS(Automatic Transfer Switch) load capacity in VA at redundancy @ (n + x) presently being used on this output phase. Here component name will be Output identifier and OutputPhase identifier with dotted separation.Possible values for OutputPhase identifier phase1(1),phase2(2),phase3(3),neutral(4).[PowerNet-MIB::atsOutputPercentLoad:1.3.6.1.4.1.318.1.1.8.5.4.3.1.10].
apc.ats.output.powerOutput Power (VA)It monitors the output power of APC ATS(Automatic Transfer Switch) in VA. Here component name will be Output identifier and OutputPhase identifier with dotted separation.Possible values for OutputPhase identifier phase1(1),phase2(2),phase3(3),neutral(4).[PowerNet-MIB::atsOutputPower:1.3.6.1.4.1.318.1.1.8.5.4.3.1.13].
apc.ats.output.power.percentOutput Power Percent%It monitors the percentage of the ATS(Automatic Transfer Switch) power capacity in VA at redundancy @ (n + x) presently being used on this output phase. Here component name will be Output identifier and OutputPhase identifier with dotted separation.Possible values for OutputPhase identifier phase1(1),phase2(2),phase3(3),neutral(4).[PowerNet-MIB::atsOutputPercentPower:1.3.6.1.4.1.318.1.1.8.5.4.3.1.16].
apc.ats.output.phase.stateOutput Phase StateIt monitors the phase load state of APC ATS (Automatic Transfer Switch). Possible values are 1: normal,2: lowload,3: nearoverload,4:overload(4).Here component name will be Output identifier and OutputPhase identifier with dotted separation.Possible values for OutputPhase identifier phase1(1),phase2(2),phase3(3),neutral(4).[PowerNet-MIB::atsOutputPhaseState:1.3.6.1.4.1.318.1.1.8.5.4.3.1.19].
apc.ats.comm.statusATS Communication StatusMonitors the current communication status of the Automatic Transfer Switch (ATS). Possible values are 1- atsNeverDiscovered,2- atsCommEstablished,3- atsCommLost.[OIDs: 1.3.6.1.4.1.318.1.1.8.5.1.1.0].
apc.ats.redundancy.stateATS Redundancy StateMonitors the current redundancy state of the ATS. atsRedundancyLost(1) indicates that the ATS is unable to switch over to the alternate power source if the current source fails. atsFullyRedundant(2) indicates that the ATS will switch over to the alternate power source if the current source fails.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.3.0].
apc.ats.over.current.stateATS Over Current StateMonitors the output current state of the ATS. atsOverCurrent(1) indicates that the ATS has exceeded the output current threshold and will not allow a switch over to the alternate power source if the current source fails. atsCurrentOK(2) indicates that the output current is below the output current threshold.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.4.0].
apc.ats.powersupply5v.stateATS 5V Power Supply StateMonitors the present state of the ATS 5V power supply. atsPowerSupplyFailure(1) indicates the 5V power supply has failed and that the ATS serial port Configuration Menu is not accessible . atsPowerSupplyOK(2) indicates that the ATS 5V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.5.0].
apc.ats.powersupply24v.stateATS 24V Power Supply StateMonitors the present state of the ATS 24V power supply for Source A. atsPowerSupplyFailure(1) indicates the 24V power supply has failed and the ATS is unable to switch over to the alternate power source if the current source fails. atsPowerSupplyOK(2) indicates that the ATS 24V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.6.0].
apc.ats.sourceB.powersupply24v.stateATS 24V Source B Power Supply StateMonitors the present state of the ATS 24V power supply for Source B. atsPowerSupplyFailure(1) indicates the 24V power supply has failed and the ATS is unable to switch over to the alternate power source if the current source fails. atsPowerSupplyOK(2) indicates that the ATS 24V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.7.0].
apc.ats.plus12v.powersupply.stateATS +12V Power Supply StateMonitors the state of the ATS 12V power supply. atsPowerSupplyFailure(1) indicates the 12V power supply has failed and the ATS is unable to monitor the current sensors. atsPowerSupplyOK(2) indicates that the ATS 12V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.8.0].
apc.ats.minus12v.powersupply.stateATS -12V Power Supply StateMonitors the present state of the ATS -12V power supply. atsPowerSupplyFailure(1) indicates the -12V power supply has failed and the ATS is unable to monitor the current sensors. atsPowerSupplyOK(2) indicates that the ATS -12V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.9.0].
apc.ats.switch.statusAutomatic Transfer Switch (ATS) StatusMonitors the status of the ATS. Possible values are 1- fail,2- ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.10.0].
apc.ats.sourceA.statusATS Source A StatusMonitors the status of the Source A. Possible values are 1- fail,2- ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.12.0].
apc.ats.sourceB.statusATS Source B StatusMonitors the status of the Source B. Possible values are 1- fail,2- ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.13.0].
apc.ats.phasesync.statusATS Phase Sync StatusMonitors the status of the phase synch. Possible values are 1- inSync,2- outOfSync.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.14.0].
apc.ats.vout.statusATS Output Voltage StatusMonitors the output voltage status. Possible values are 1-fail,2-ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.15.0].
apc.ats.hardware.statusATS Hardware StatusMonitors the status of display board hardware.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.16.0].

APC Hardware Status Monitors

Description

Monitors the APC hardware status such as APC External Environment Status,APC Integrated Environment Status,APC Environmental Management System Status,APC Rack Air Removal Unit Status,APC MasterSwitch Unit Status,APC MasterSwitch VM Unit Status,APC MasterSwitch Plus Unit Status,APC Automatic Transfer Switch(ATS) Status,APC NetworkAir FM System Status.

Prerequisites

No prerequisite

Supported Metric

Monitor NameMetric NameMetric Display NameUnitDescription
APC Status Monitorsapc.ext.envmon.comm.statusExternal Environment Monitor StatusMonitors the communication status between the agent and the Environmental Monitor. Possible values are 1- noComm: Communication has never been established,2- comm: Communication has been established,3- commLost: Communication was established,but was lost.[OID: 1.3.6.1.4.1.318.1.1.10.1.3.1.0].
apc.ats.comm.statusATS Communication StatusMonitors the current communication status of the Automatic Transfer Switch (ATS). Possible values are 1- atsNeverDiscovered,2- atsCommEstablished,3- atsCommLost.[OIDs: 1.3.6.1.4.1.318.1.1.8.5.1.1.0].
apc.ats.redundancy.stateATS Redundancy StateMonitors the current redundancy state of the ATS. atsRedundancyLost(1) indicates that the ATS is unable to switch over to the alternate power source if the current source fails. atsFullyRedundant(2) indicates that the ATS will switch over to the alternate power source if the current source fails.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.3.0].
apc.ats.over.current.stateATS Over Current StateMonitors the output current state of the ATS. atsOverCurrent(1) indicates that the ATS has exceeded the output current threshold and will not allow a switch over to the alternate power source if the current source fails. atsCurrentOK(2) indicates that the output current is below the output current threshold.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.4.0].
apc.ats.powersupply5v.stateATS 5V Power Supply StateMonitors the present state of the ATS 5V power supply. atsPowerSupplyFailure(1) indicates the 5V power supply has failed and that the ATS serial port Configuration Menu is not accessible . atsPowerSupplyOK(2) indicates that the ATS 5V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.5.0].
apc.ats.powersupply24v.stateATS 24V Power Supply StateMonitors the present state of the ATS 24V power supply for Source A. atsPowerSupplyFailure(1) indicates the 24V power supply has failed and the ATS is unable to switch over to the alternate power source if the current source fails. atsPowerSupplyOK(2) indicates that the ATS 24V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.6.0].
apc.ats.sourceB.powersupply24v.stateATS 24V Source B Power Supply StateMonitors the present state of the ATS 24V power supply for Source B. atsPowerSupplyFailure(1) indicates the 24V power supply has failed and the ATS is unable to switch over to the alternate power source if the current source fails. atsPowerSupplyOK(2) indicates that the ATS 24V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.7.0].
apc.ats.plus12v.powersupply.stateATS +12V Power Supply StateMonitors the state of the ATS 12V power supply. atsPowerSupplyFailure(1) indicates the 12V power supply has failed and the ATS is unable to monitor the current sensors. atsPowerSupplyOK(2) indicates that the ATS 12V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.8.0].
apc.ats.minus12v.powersupply.stateATS -12V Power Supply StateMonitors the present state of the ATS -12V power supply. atsPowerSupplyFailure(1) indicates the -12V power supply has failed and the ATS is unable to monitor the current sensors. atsPowerSupplyOK(2) indicates that the ATS -12V power supply is operating within tolerance.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.9.0].
apc.ats.switch.statusAutomatic Transfer Switch (ATS) StatusMonitors the status of the ATS. Possible values are 1- fail,2- ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.10.0].
apc.ats.sourceA.statusATS Source A StatusMonitors the status of the Source A. Possible values are 1- fail,2- ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.12.0].
apc.ats.sourceB.statusATS Source B StatusMonitors the status of the Source B. Possible values are 1- fail,2- ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.13.0].
apc.ats.phasesync.statusATS Phase Sync StatusMonitors the status of the phase synch. Possible values are 1- inSync,2- outOfSync.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.14.0].
apc.ats.vout.statusATS Output Voltage StatusMonitors the output voltage status. Possible values are 1-fail,2-ok.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.15.0].
apc.ats.hardware.statusATS Hardware StatusMonitors the status of display board hardware.[OID: 1.3.6.1.4.1.318.1.1.8.5.1.16.0].
apc.airfmsys.present.statusAir FM System Present StatusMonitors the present mode of the System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. Possible values are 1- notApplicable,2- reserved1,3- reserved2,4- onLine,5- idle,6- loadShare,7- failed,8- offLine.[OID: 1.3.6.1.4.1.318.1.1.13.1.4.1.2.0].
APC Air FM System Input Statusapc.airfmsys.input.statusAir FM System Input StatusMonitors the state of this contact: Open(1) or Closed(2). A violation will occur when this relay is not in its normal state.[OIDs: 1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.3,1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.3].
APC Air FM System Output Statusapc.airfmsys.ouput.statusAir FM System Output StatusMonitors the state of this contact: Open(1) or Closed(2). A violation will occur when this relay is not in its normal state.[OIDs: 1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.2,1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.3].
APC EMS Alarm Device Stateapc.ems.alarm.device.stateEMS Alarm Device StateMonitors the alarm device state. Possible values are 1- alarmDeviceOnEMS: device is active,2- alarmDeviceOffEMS: device is inactive,3- alarmDeviceNotInstalledEMS: device is not installed.[OIDs: 1.3.6.1.4.1.318.1.1.10.3.17.1.1.2,1.3.6.1.4.1.318.1.1.10.3.17.1.1.3].
APC EMS Communication Statusapc.ems.comm.statusEMS Communication StatusMonitors the communication status between the agent and the Environment Management System (EMS). Possible values are 1- noComm: Communication has never been established,2- comm: Communication has been established,3- commLost: Communication was established,but was lost.[OIDs: 1.3.6.1.4.1.318.1.1.10.3.12.1,1.3.6.1.4.1.318.1.1.10.3.12.2].
APC EMS Input Contact Stateapc.ems.input.contact.stateEMS Input Contact StateMonitors the state of the input contact. Possible values are 1- contactClosedEMS: input contact is closed,2- contactOpenEMS : input contact state is open.[OIDs: 1.3.6.1.4.1.318.1.1.10.3.14.1.1.2,1.3.6.1.4.1.318.1.1.10.3.14.1.1.3].
APC EMS Outlet Stateapc.ems.outlet.stateEMS Outlet StateMonitors the state of the outlet. Possible values are 1- outletOnEMS: outlet is on,2- outletOffEMS: outlet is off.[OIDs: 1.3.6.1.4.1.318.1.1.10.3.16.1.1.2,1.3.6.1.4.1.318.1.1.10.3.16.1.1.3].
APC EMS Probe Communication Statusapc.ems.probe.comm.statusEMS Probe Communication StatusMonitors the state of communications to the probe. Possible values are 1- commsNeverDiscovered: indicates there has never been communications with this device,2- commsEstablished: indicates communication is normal and active with this device,3- commsLost: indicates communication had been established,but is no longer.[OIDs: 1.3.6.1.4.1.318.1.1.10.3.13.1.1.2,1.3.6.1.4.1.318.1.1.10.3.13.1.1.10].
APC EMS Relay Stateapc.ems.outrelay.statusEMS Output Relay StateMonitors the state of the output relay. Possible values are 1- relayClosedEMS: output relay is closed,2- relayOpenEMS : output relay is open.[OIDs: 1.3.6.1.4.1.318.1.1.10.3.15.1.1.2,1.3.6.1.4.1.318.1.1.10.3.15.1.1.3].
APC EMS Sensor Stateapc.ems.sensor.stateEMS Sensor StateMonitors the sensor state. Possible values are 1- sensorFaultedEMS: sensor is faulted,2- sensorOKEMS: sensor is not faulted,3- sensorNotInstalledEMS: sensor is not installed.[OIDs: 1.3.6.1.4.1.318.1.1.10.3.18.1.1.3,1.3.6.1.4.1.318.1.1.10.3.18.1.1.4].
APC External Environment Probe Statusapc.ext.envmon.probe.statusExternal Environment Probe StatusMonitors the connected status of the probe,either disconnected(1) or connected(2).[OIDs: 1.3.6.1.4.1.318.1.1.10.1.3.3.1.3,1.3.6.1.4.1.318.1.1.10.1.3.3.1.2].
APC Integrated Environment Probe Statusapc.integrated.envmon.probe.statusIntegrated Environment Probe StatusMonitors the connected status of the probe,either disconnected(1) or connected(2).[OIDs: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.2,1.3.6.1.4.1.318.1.1.10.2.3.2.1.3].
APC Integrated Environment Relay Statusapc.integrated.envmon.outrelay.statusIntegrated Environment Output Relay StatusMonitors the status of the output relay,either faultState(1) or normalState(2).[OIDs: 1.3.6.1.4.1.318.1.1.10.2.3.7.1.2,1.3.6.1.4.1.318.1.1.10.2.3.7.1.3].
APC MasterSwitch Plus Outlet Stateapc.masterswitchplus.outlet.stateMasterSwitch Plus Outlet StateMonitors the outlet state. If the outlet is on,the outletStatusMSPOn (1) value will be returned. If the outlet is off,the outletStatusMSPOff (2) value will be returned.[OIDs: 1.3.6.1.4.1.318.1.1.6.7.1.1.2,1.3.6.1.4.1.318.1.1.6.7.1.1.4,1.3.6.1.4.1.318.1.1.6.7.1.1.5].
APC MasterSwitch VM Current Loadapc.masterswitchvm.current.loadMasterSwitch VM Current Load%Monitors the total amount of power being consumed by the load. It is represented as a percentage of full load.[OIDs: 1.3.6.1.4.1.318.1.1.5.4.2.1.2,1.3.6.1.4.1.318.1.1.5.4.2.1.6].
APC MasterSwitch VM Outlet Stateapc.masterswitchvm.outlet.stateMasterSwitch VM Outlet StateMonitors the outlet state. If the outlet is on,the outletStatusOnVM (1) value will be returned. If the outlet is off,the outletStatusOffVM (2) value will be returned.[OIDs: 1.3.6.1.4.1.318.1.1.5.7.1.1.2,1.3.6.1.4.1.318.1.1.5.7.1.1.4,1.3.6.1.4.1.318.1.1.5.7.1.1.5].
APC Rack Air Removal Unit Statusapc.aru.alarm.statusARU Alarm StatusMonitors the current alarm state of the Air Removal Unit (ARU). If the state of the ARU is unknown,this variable is set to 'UNKNOWN'. It is an ASCII string containing the 8 flags. The flags are defined as follows:
Flag 1: Fan Fail 1
Flag 2: Fan Fail 2
Flag 3: Fan Fail 3
Flag 4: Smoke (if ARU is equipped with smoke detector)
Flag 5: High Temp (Out of Thermal Control)
Flag 6: Over Temp (Exhaust Temp. Exceeds Override Setpoint)
Flag 7: Fan Fail 4 (Gen 2 ARU only)
Flag 8: Reserved.[OIDs: 1.3.6.1.4.1.318.1.1.14.3.3.1.2,1.3.6.1.4.1.318.1.1.14.3.3.1.10].
apc.aru.comm.statusARU Communication StatusMonitors the state of communications to the device. Possible values are 1- commsNeverDiscovered: there has never been communications with this device,2- commsEstablished: communication is normal and active with this device,3- commsLost: communication had been established,but is no device.[OIDs: 1.3.6.1.4.1.318.1.1.14.3.3.1.2,1.3.6.1.4.1.318.1.1.14.3.3.1.2].

APC NetShelter Advanced Rack PDU Hardware Monitors

Description

Template to monitor the APC NetShelter Advanced Rack PDU Hardware Statistics like Circuit Breaker,External Sensor,Outlet Metered Status,Outlet Switched Control State,Outlet Switched Current Rating,Outlet Switched StartUp State,Outlet Switched State,Smart Cabinet Control,Input Phase,Unit Power Share,Voltage,Frequency,Current,Load State,Active Power and Energy.[PowerNet-MIB :: pduCircuitBreakerStatusLoadState : 1.3.6.1.4.1.318.1.1.32.4.4.1.4,pduCircuitBreakerStatusCurrent : 1.3.6.1.4.1.318.1.1.32.4.4.1.5,pduExternalSensorStatusCommStatus : 1.3.6.1.4.1.318.1.1.32.6.4.1.3,pduExternalSensorStatusState : 1.3.6.1.4.1.318.1.1.32.6.4.1.4,pduOutletMeteredStatusLoadState : 1.3.6.1.4.1.318.1.1.32.5.9.1.4,pduOutletMeteredStatusCurrent : 1.3.6.1.4.1.318.1.1.32.5.9.1.5,pduOutletMeteredStatusActivePower : 1.3.6.1.4.1.318.1.1.32.5.9.1.6,pduOutletSwitchedControlCommand : 1.3.6.1.4.1.318.1.1.32.5.5.1.4,pduOutletSwitchedPropertiesCurrentRating : 1.3.6.1.4.1.318.1.1.32.5.3.1.6,pduOutletSwitchedStateOnStartup : 1.3.6.1.4.1.318.1.1.32.5.2.1.3,pduOutletSwitchedStatusState : 1.3.6.1.4.1.318.1.1.32.5.4.1.4,pduUnitSmartCabinetControlUserName : 1.3.6.1.4.1.318.1.1.32.7.3.1.0,pduUnitSmartCabinetControlCardID : 1.3.6.1.4.1.318.1.1.32.7.3.2.0,pduUnitSmartCabinetControlDoor : 1.3.6.1.4.1.318.1.1.32.7.3.4.0,pduUnitSmartCabinetColdAisleLockStatus : 1.3.6.1.4.1.318.1.1.32.7.3.6.0,pduUnitSmartCabinetHotAisleLockStatus : 1.3.6.1.4.1.318.1.1.32.7.3.7.0,pduInputPhaseStatusCurrentState : 1.3.6.1.4.1.318.1.1.32.3.4.1.3,pduInputPhaseStatusVoltageState : 1.3.6.1.4.1.318.1.1.32.3.4.1.4,pduInputPhaseStatusCurrent: 1.3.6.1.4.1.318.1.1.32.3.4.1.5,pduInputPhaseStatusVoltage : 1.3.6.1.4.1.318.1.1.32.3.4.1.6,pduInputPhaseStatusActivePower : 1.3.6.1.4.1.318.1.1.32.3.4.1.7,pduUnitPsSupportUpstreamStatus : 1.3.6.1.4.1.318.1.1.32.2.4.1.2,pduUnitPsSupportDownstreamStatus : 1.3.6.1.4.1.318.1.1.32.2.4.1.3,pduUnitPsOptMode : 1.3.6.1.4.1.318.1.1.32.2.4.1.4,pduUnitPropertiesRatedVoltage : 1.3.6.1.4.1.318.1.1.32.2.3.1.10,pduUnitPropertiesRatedMaxCurrent : 1.3.6.1.4.1.318.1.1.32.2.3.1.11,pduUnitPropertiesRatedFrequency : 1.3.6.1.4.1.318.1.1.32.2.3.1.12,pduUnitPropertiesRatedPower : 1.3.6.1.4.1.318.1.1.32.2.3.1.13,pduUnitStatusLoadState : 1.3.6.1.4.1.318.1.1.32.2.4.1.3,pduUnitStatusActivePower : 1.3.6.1.4.1.318.1.1.32.2.4.1.4,pduUnitStatusEnergy : 1.3.6.1.4.1.318.1.1.32.2.4.1.9]

Prerequisites

The Device Should have Support for the PowerNet-MIB

Supported Metric

Monitor NameMetric NameMetric Display NameUnitDescription
APC cPDU - Circuit Breakerapc_cPDU_CircuitBreaker_LoadStateAPC cPDU Circuit Breaker Load statusMonitors the APC PDU Circuit Breaker present Load Status. Possible values are 1- upperCritical,2- upperWarning,3- lowerWarning,4- lowerCritical,5- normal,6- off.[PowerNet-MIB :: pduUnitStatusLoadState : 1.3.6.1.4.1.318.1.1.32.4.4.1.4]
apc_cPDU_CircuitBreaker_CurrentAPC cPDU Circuit Breaker CurrentampsMonitors the PDU Circuit Breaker Current in hundredths of Amps.[PowerNet-MIB :: pduCircuitBreakerStatusCurrent : 1.3.6.1.4.1.318.1.1.32.4.4.1.5]
APC cPDU - External Sensorapc_cPDU_ExternalSensor_CommStatusAPC cPDU Sensor Communication StatusMonitors the Communications Status of the Sensor.Possible Values are 0- notInstalled,1- commsOk,2- commsLost.[PowerNet-MIB :: pduExternalSensorStatusCommStatus : 1.3.6.1.4.1.318.1.1.32.6.4.1.3]
apc_cPDU_ExternalSensor_StateAPC cPDU Sensor Current StatusMonitors the External Sensor Current Status. Possible Value are 0- notPresent,1- alarmed,2- normal,3- belowLowerCritical,4- belowLowerWarning,5- aboveUpperWarning,6- aboveUpperCritical.[PowerNet-MIB :: pduExternalSensorStatusState : 1.3.6.1.4.1.318.1.1.32.6.4.1.4]
APC cPDU - Outlet Metered Statusapc_cPDU_OutletMetered_LoadStateAPC cPDU Outlet Metered Load StatusMonitors the Present Load Status of the PDU Metered Outlet.Possible values are 1- upperCritical,2- upperWarning,3- lowerWarning,4- lowerCritical,5- normal.[PowerNet-MIB :: pduOutletMeteredStatusLoadState : 1.3.6.1.4.1.318.1.1.32.5.9.1.4]
apc_cPDU_OutletMetered_ActivePowerAPC cPDU Outlet Metered PowerWMonitors the APC PDU Power in Watts,of the Load on the PDU outlet.[PowerNet-MIB :: pduOutletMeteredStatusActivePower : 1.3.6.1.4.1.318.1.1.32.5.9.1.6]
apc_cPDU_OutletMetered_CurrentAPC cPDU Outlet Metered CurrentampsMonitors the APC PDU Current,in hundredths of Amps,on the PDU outlet.[PowerNet-MIB :: pduOutletMeteredStatusCurrent : 1.3.6.1.4.1.318.1.1.32.5.9.1.5]
APC cPDU - Outlet Switched Control Stateapc_cPDU_OutletSwitched_ControlCommandAPC cPDU Switched Outlet Control StateMonitors the APC PDU Switched Outlet Control State.Possible Values are 1- immediateOff,2-immediateOn,3- delayedOff,4- delayedOn,5-immediateReboot,6- delayedReboot(6) 7- outletUnknown.[PowerNet-MIB :: pduOutletSwitchedControlCommand : 1.3.6.1.4.1.318.1.1.32.5.5.1.4]
APC cPDU - Outlet Switched Current Ratingapc_cPDU_OutletSwitched_CurrentRatingAPC cPDU Outlet Switched Current RatingampsMonitors the Current Rating of Outlet in hundreths of Ampere.[PowerNet-MIB :: pduOutletSwitchedPropertiesCurrentRating : 1.3.6.1.4.1.318.1.1.32.5.3.1.6]
APC cPDU - Outlet Switched StartUp Stateapc_cPDU_OutletSwitched_StateOnStartupAPC cPDU Switched Outlet StateMonitors the APC PDU Switched Outlet State on device startup.Possible Values are 0- off,1- on,2- lastKnownState.[PowerNet-MIB :: pduOutletSwitchedStateOnStartup : 1.3.6.1.4.1.318.1.1.32.5.2.1.3]
APC cPDU - Outlet Switched Stateapc_cPDU_OutletSwitched_StateAPC cPDU Switched Outlet Switch StateMonitors the APC PDU present switch state of switched outlet.Possible Values are 1- on,0-off.[PowerNet-MIB :: pduOutletSwitchedStatusState : 1.3.6.1.4.1.318.1.1.32.5.4.1.4]
APC cPDU - Smart Cabinet Controlapc_cPDU_SmartCabinet_UserNameAPC cPDU Smart Cabinet UserNameMonitors the PDU Smart Cabinet UserName.[PowerNet-MIB :: pduUnitSmartCabinetControlUserName : 1.3.6.1.4.1.318.1.1.32.7.3.0]
apc_cPDU_SmartCabinet_CardIDAPC cPDU Smart Cabinet Card IDMonitors the APC PDU Smart Cabinet Card ID.[PowerNet-MIB :: pduUnitSmartCabinetControlCardID : 1.3.6.1.4.1.318.1.1.32.7.3.2.0]
apc_cPDU_SmartCabinet_DoorAPC cPDU Smart Cabinet DoorMonitors the APC PDU Aisle of Smart Cabinet.[PowerNet-MIB :: pduUnitSmartCabinetControlDoor : 1.3.6.1.4.1.318.1.1.32.7.3.4.0]
apc_cPDU_SmartCabinet_ColdAisleLockStatusAPC cPDU Smart Cabinet Cold Aisle Lock StateMonitors the APC PDU Smart Cabinet ColdAisle lock state.[PowerNet-MIB :: pduUnitSmartCabinetColdAisleLockStatus : 1.3.6.1.4.1.318.1.1.32.7.3.6.0]
apc_cPDU_SmartCabinet_HotAisleLockStatusAPC cPDU Smart Cabinet Hot Aisle Lock StateMonitors the APC PDU Smart Cabinet HotAisle lock state.[PowerNet-MIB :: pduUnitSmartCabinetHotAisleLockStatus: 1.3.6.1.4.1.318.1.1.32.7.3.7.0]
APC cPDU - Input Phaseapc_cPDU_InputPhase_CurrentStateAPC cPDU Input Phase Current StateMonitors the APC PDU present current status.Possible values are 1- upperCritical,2- upperWarning,3- lowerWarning,4- lowerCritical,5- normal.[PowerNet-MIB :: pduInputPhaseStatusCurrentState : 1.3.6.1.4.1.318.1.1.32.3.4.1.3]
apc_cPDU_InputPhase_VoltageStateAPC cPDU Input Phase Voltage StateMonitors the APC PDU present voltage status of the PDU Input Phase.Possible values are 1- upperCritical,2- upperWarning,3- lowerWarning,4- lowerCritical,5- normal.[PowerNet-MIB :: pduOutletSwitchedStatusState : 1.3.6.1.4.1.318.1.1.32.5.4.1.4]
apc_cPDU_InputPhase_VoltageStatusAPC cPDU Input Phase Voltage StatusvMonitors the APC PDU Input Phase voltage,in Volts(V)[PowerNet-MIB :: pduInputPhaseStatusVoltage : 1.3.6.1.4.1.318.1.1.32.3.4.1.6]
apc_cPDU_InputPhase_ActivePowerAPC cPDU Input Phase PowerWMonitors the APC PDU present power consumption,in Watts.[PowerNet-MIB :: pduInputPhaseStatusActivePower : 1.3.6.1.4.1.318.1.1.32.3.4.1.7]
apc_cPDU_InputPhase_CurrentStatusAPC cPDU Input phase CurrentampsMonitors the PDU Input phase current in hundredths of Amps.[PowerNet-MIB :: pduInputPhaseStatusCurrent : 1.3.6.1.4.1.318.1.1.32.3.4.1.5]
APC cPDU - Unit Power Shareapc_cPDU_PowerShare_UpstreamStatusAPC cPDU Power Share Upstream StatusMonitors the PDU Power Share UpstreamStatus. Possible Values are 0- notAvailable,1- available.[PowerNet-MIB :: pduUnitPsSupportUpstreamStatus : 1.3.6.1.4.1.318.1.1.32.2.5.1.2]
apc_cPDU_PowerShare_DownstreamStatusAPC cPDU Power Share DownstreamStatusMonitors the Power share support status on downstream PDU. Possible Values are 0- notAvailable,1- available.[PowerNet-MIB :: pduUnitPsSupportDownstreamStatus : 1.3.6.1.4.1.318.1.1.32.2.5.1.3]
apc_cPDU_PowerShare_OptModeAPC cPDU Power Operating ModeMonitors the PDU Operating power status. Possible Values are 0- backupPower,1- mainPower.[PowerNet-MIB :: pduUnitPsOptMode : 1.3.6.1.4.1.318.1.1.32.2.5.1.4]
APC cPDU - Unit Propertiesapc_cPDU_RatedVoltageAPC cPDU Voltage RatingvMonitors the APC PDU Voltage Rating in Volts.[PowerNet-MIB :: pduUnitPropertiesRatedVoltage : 1.3.6.1.4.1.318.1.1.32.2.3.1.10]
apc_cPDU_RatedMaxCurrentAPC cPDU Current RatingampsMonitors the APC PDU Current Rating in Amps.[PowerNet-MIB :: pduUnitPropertiesRatedMaxCurrent : 1.3.6.1.4.1.318.1.1.32.2.3.1.11]
apc_cPDU_RatedFrequencyAPC cPDU Frequency RatingHzMonitors the APC PDU Frequency Rating in Hz.[PowerNet-MIB :: pduUnitPropertiesRatedFrequency : 1.3.6.1.4.1.318.1.1.32.2.3.1.12]
apc_cPDU_RatedPowerAPC cPDU Power RatingWMonitors the APC PDU Power Rating in (VoltAmps).[PowerNet-MIB :: pduUnitPropertiesRatedPower : 1.3.6.1.4.1.318.1.1.32.2.3.1.13]
APC cPDU - Unit Statusapc_cPDU_LoadStateAPC cPDU Load StatusMonitors the present Load Status of the APC PDU based on Active Power.Possible values are 1- upperCritical,2- upperWarning,3- lowerWarning,4- lowerCritical,5- normal.[PowerNet-MIB :: pduUnitStatusLoadState : 1.3.6.1.4.1.318.1.1.32.2.4.1.3]
apc_cPDU_ActivePowerAPC cPDU Active Power ConsumedWMonitors the power consumption,in Watts(W).[PowerNet-MIB :: pduUnitStatusActivePower : 1.3.6.1.4.1.318.1.1.32.2.4.1.4]
apc_cPDU_EnergyAPC cPDU Energy ConsumedWMonitors the APC PDU Total Energy Consumed,in tenths of Kilowatt-Hours(kWh),of the PDU over its lifetime.[PowerNet-MIB :: pduUnitStatusEnergy : 1.3.6.1.4.1.318.1.1.32.2.4.1.9]

APC Rack PDU Status - G2

Description

Template for Power Distribution unit. Performs application monitoring on PDU bank state,load state,master switch state,outlet state etc,.

Prerequisites

No prerequisite

Supported Metric

Monitor NameMetric NameMetric Display NameUnitDescription
APC PDU Load Statepdu.load.statePDU Load StateIndicates the phase/bank load status. phaseLoadNormal(1) indicates that the phase is operating properly within the rPDULoadConfigLowLoadThreshold and rPDULoadConfigNearOverloadThreshold OID values. phaseLoadLow(2) indicates that the phase load has dropped below the rPDULoadConfigLowLoadThreshold OID value. phaseLoadNearOverload(3) indicates that the phase load is greater than or equal to the rPDULoadConfigNearOverloadThreshold OID value. phaseLoadOverload(4) indicates that the phase load is greater than or equal to the rPDULoadConfigOverloadThreshold OID value.[OID: 1.3.6.1.4.1.318.1.1.12.2.3.1.1.3].
pdu.current.loadPDU Current LoadampsAPC PDU phase/bank current load in amps.[OIDs: 1.3.6.1.4.1.318.1.1.12.2.3.1.1.2].
APC PDU Outlet Statepdu.outlet.statePDU Outlet StateProvides the name and the state of the outlet. Possible values are 1-Outlet On,2- Outlet Off,3- Outlet Reboot,4- Outlet Unknown,5- Outlet On With Delay,6- Outlet Off With Delay,7- Outlet Reboot With Delay.[OID: 1.3.6.1.4.1.318.1.1.4.4.2.1.3].
APC PDU Outlet Statisticspdu.controlled.outletsPDU Controlled OutletsThe number of controlled outlets on this Switched Rack PDU.[OID: 1.3.6.1.4.1.318.1.1.12.3.1.3.0].
pdu.total.outletsPDU Total OutletsThe total number of outlets on this Rack PDU.[OID: 1.3.6.1.4.1.318.1.1.12.3.1.4.0].
pdu.monitored.outletsPDU Monitored OutletsRepresents the PDU Outlets Monitored.[OID: 1.3.6.1.4.1.318.1.1.12.3.1.5.0].
pdu.power.supply.statusPDU Power Supply StatusIndicates the PowerSupply alarm. Possible values are 1- All Available Power Supplies OK,2- Power Supply One Failed,3- Power Supply Two Failed,4- Power Supply One and Two Failed.[OID: 1.3.6.1.4.1.318.1.1.12.4.1.3.0].
APC PDU Bank Statepdu.bank.statePDU Bank StateProvides the index to the RACK PDU Bank entry and the bank load state. Possible values are 1- Bank Load Normal,2- Bank Load Low,3- Bank Load Never Overlaod,4- Bank Load Overload.[OID: 1.3.6.1.4.1.318.1.1.12.5.2.1.3].
APC PDU Load Bank Configuration Alarmpdu.loadbank.config.alarmPDU Load Bank Configuration AlarmProvides the current bank load alarm state. Possible alarm status values are 1- No Load Alarm,2- Under Current Alarm,3- Near Over Current Alarm,4- Over Current Alarm.[OID: 1.3.6.1.4.1.318.1.1.12.2.4.1.1.5].
APC PDU Master Switch Statepdu.master.switch.statePDU Master Switch StateMonitors the status of all outlets.[OID: 1.3.6.1.4.1.318.1.1.4.2.2.0].

APC UPS Battery Last Replace And Manufacture Days

Description

This template provides the number of days since the UPS system’s batteries were last replaced and UPS was manufactured.[PowerNet-MIB :: upsBasicBatteryLastReplaceDate : 1.3.6.1.4.1.318.1.1.1.2.1.3.0,upsAdvIdentDateOfManufacture : 1.3.6.1.4.1.318.1.1.1.1.2.2.0]

Prerequisites

NULL

Supported Metric

Monitor NameMetric NameMetric Display NameUnitDescription
APC UPS Battery Last Replace And Manufacture Daysapc_ups_BatteryLastReplaceDaysAPC UPS Battery Last Replace DaysDaysMonitor provides the number of days since the UPS system's batteries were last replaced.[PowerNet-MIB :: upsBasicBatteryLastReplaceDate : 1.3.6.1.4.1.318.1.1.1.2.1.3.0]
apc_ups_ManufactureDaysAPC UPS Manufacture DaysDaysThis monitor provides the number of days since the UPS was manufactured.[PowerNet-MIB :: upsAdvIdentDateOfManufacture : 1.3.6.1.4.1.318.1.1.1.1.2.2.0]

APC UPS Status Check - G2

Description

Template for monitoring APC UPS. Monitors battery capacity,battery status,run time remaining,temperature,input line voltage,output line voltage,etc. Tested on APC Web/SNMP Management Card. System Object Id: 1.3.6.1.4.1.318.1.3.27.

Prerequisites

No prerequisite

Supported Metric

Monitor NameMetric NameMetric Display NameUnitDescription
APC UPS Monitorsups.battery.statusUPS Battery statusIndicates the status of the UPS batteries. Possible status values are 1 - Unknown,2 - Battery Normal,3 - Battery Low.[OID: 1.3.6.1.4.1.318.1.1.1.2.1.1].
ups.no.of.batter.packs.badUPS No Of Bad Battery PacksThe number of external battery packs connected to the UPS that are defective.[OID: 1.3.6.1.4.1.318.1.1.1.2.2.6].
ups.battery.capacityUPS Battery Capacity%The remaining battery capacity expressed in percent of full capacity. Alert is generated when the battery capacity is less than 99%.[OID: 1.3.6.1.4.1.318.1.1.1.2.2.1.0].
ups.battery.replace.indicatorUPS Battery Replace IndicatorIndicates whether the UPS batteries need replacing. Possible values are 1 - No Battery Needs Replacing,2 - Battery Needs Replacing.[OID: 1.3.6.1.4.1.318.1.1.1.2.2.4].
ups.battery.runtime.remainingUPS Battery Runtime RemainingsIndicates the UPS battery run time remaining before battery exhaustion.[OID: 1.3.6.1.4.1.318.1.1.1.2.2.3.0].
ups.battery.temperatureUPS Battery TemperatureCelsiusThe current internal UPS temperature expressed in Celsius.[OID: 1.3.6.1.4.1.318.1.1.1.2.2.2.0].
ups.inputline.voltageUPS Input Line VoltagevIndicates the current utility line voltage in VAC.[OID: 1.3.6.1.4.1.318.1.1.1.3.2.1.0].
ups.frequency.outputUPS Output FrequencyHzIndicates the current output frequency of the UPS system in Hz.[OID: 1.3.6.1.4.1.318.1.1.1.4.2.2].
ups.load.outputUPS Output Load%Indicates the current UPS load expressed in percent of rated capacity.[OID: 1.3.6.1.4.1.318.1.1.1.4.2.3].
ups.status.outputUPS Output StatusIndicates that the UPS is not supplying line voltage to any attached devices. Possible status values are 1 -Unknown,2 - On Line,3 - On Battery,4 - On Smart boost,5 - Timed Sleeping,6 - Software Bypass,7 - Off,8 - Rebooting,9 - Switched Bypass,10-hardwareFailureBypass 11-SleepingUntilPowerReturn 12-onSmartTrim,13-ecoMode,14-hotStandby,15-onBatteryTest.[OID: 1.3.6.1.4.1.318.1.1.1.4.1.1].
ups.voltage.outputUPS Output VoltagevIndicates the output voltage of the UPS system in VAC.[OID: 1.3.6.1.4.1.318.1.1.1.4.2.1].
ups.battery.timeUPS Time On BatterysThe elapsed time since the UPS has switched to battery power. Alert is generated when the time on battery is greater than 0 seconds.[OID: 1.3.6.1.4.1.318.1.1.1.2.1.2].